Table 4-11: TFIO combo digital module and extended
J1
1
POINT 1 SIG
2
POINT 1 GND
3
POINT 2 SIG
4
POINT 2 GND
Table 4-12: TFIO thermocouple module
J1
1
Shield
2
TC1 (J-Wht/K-Yel)
3
TC1 Red (-)
4
Shield
Table 4-13: TFIO RTD module
J1
1
OUT
2
(+)
3
(-)
4
IN
See section
8.6
to configure the TFIO interfaces.
5
Power the RMC
This section describes two modes for powering the controller:
Battery mode: Power is supplied by a 12 volt battery with a charger (see section 5.2.)
External power mode: Power is supplied by an external power source (see section 5.3.)
Review section 5.1, follow the instructions for the appropriate power mode, then continue to section
Lithium
battery.
NOTICE – Equipment damage. Power compatibility for TFIO modules depends on module
generation:
Older green modules must only use 12 Vdc.
M2 modules and newer gray modules can use 12 or 24 Vdc.
A combination of green modules and M2 modules or gray modules must only use 12
Vdc.
5.1
Power on sequence
The RMC power on sequence is initiated as soon as power is connected. The following information may be
displayed on the LCD as the controller completes its startup:
ABB TOTALFLOW RMC-100: identifies the controller name and model
BOOT 2105412-XXX: indicates the version of the boot software
OS 2105411-XXX: indicates the version of the operating system
Super CAP Charged: indicates if the super capacitor is charged (see section 5.1.1.)
APP 2105457-XXX: indicates the flash version
IMPORTANT NOTE: The scrolling duration of the displayed items may vary. When the
DATE/TIME displays, the power on sequence is completed.
J2
POINT 3 SIG
POINT 3 GND
POINT 4 SIG
POINT 4 GND
J2
Shield
TC2 (J-Wht/K-Yel)
TC2 Red (-)
Shield
J2
OUT
(+)
(-)
IN
J3
POINT 5 SIG
POINT 5 GND
POINT 6 SIG
POINT 6 GND
J3
Shield
TC3 (J-Wht/K-Yel)
TC3 Red (-)
Shield
J3
OUT
(+)
(-)
IN
2105551M NAD | RM C-100 | 17
J4
POINT 7 SIG
POINT 7 GND
POINT 8 SIG
POINT 8 GND
J4
Shield
TC4 (J-Wht/K-Yel)
TC4 Red (-)
Shield
J4
OUT
(+)
(-)
IN
5.4