2.4
CC-Link IE Field Network function
 CC-Link IE Field Network communication specifications
Item
Transmission speed
Communication method
Number of units connected
Maximum distance between nodes
Maximum number of branches
Topology
Connection cable
Connector
Node type
RX
RY
Maximum cyclic size (of one node)
RWr
RWw
 Parts
NOTE
• Do not remove the CC-Link IE Field Network communication circuit board or the earth plate.
 Connection cable
For wiring, use the 1000BASE-T compliant Ethernet cables.
Ethernet cable
Category 5e or higher
(Double shielded/STP) Straight cable
NOTE
• For CC-Link IE Field Network wiring, use the recommended wiring components by CC-Link Partner Association.
• Cables for CC-Link IE Controller Network cannot be used for CC-Link IE Field Network.
• Depending on the cable connector shape, the cable may not be able to be connected to the communication connector.
1 Gbps
Token passing
120 units at max. (64 units when all stations are inverters handling 128-word transmissions.)
Different devices can be connected together.
100 m
No upper limit within the same Ethernet system
Line, star, ring, or a combination of line and star
Ethernet cable
(IEEE 802.3 1000BASE-T compliant cable or ANSI/TIA/EIA-568-B (Category 5e) compliant shielded 4-pair branched cable)
Shielded RJ-45
Intelligent device station
64 bits
64 bits
128 words
128 words
RUN D LINK
SD
ERR
RD L.ERR
Connector
RJ-45 connector
CC-Link IE Field Network function
Description
CC-Link IE Field Network communication
circuit board
Operation status indication LED
Connector for communication (PORT2)
Connector for communication (PORT1)
Earth plate
Type
The following conditioning cables:
• IEEE802.3 (1000BASE-T)
• ANSI/TIA/EIA-568-B (Category 5e)
13
WIRING