Siemens 3AH3 Instruction Manual page 35

Vacuum circuit breaker operator modules 4.16 kv to 38 kv

Advertisement

Table 3: Typical vacuum interrupter contact life expectancy
Rated maximum
Interrupting class
voltage kV
MVA
4.76
4.76
8.25
15.0
15.0
15.0
1,000
38.0
1,500
Rated maximum
Interrupting class
voltage kV
4.76
4.76
4.76
4.76
8.25
15.0
15.0
15.0
15.0
15.0
15.0
15.5
15.5
15.5
15.5
27.6
27.6
38.0
38.0
38.0
38.0
Footnote:
Maximum symmetrical interrupting current rating of circuit breaker (refer to Tables 11 and 12).
1.
Rated short-circuit current
250
29 kA @ 4.76 kV; 36 kA @ 3.85 kV
350
41 kA @ 4.76 kV; 49 kA @ 4.0 kV
500
33 kA @ 8.25 kV; 41 kA @ 6.6 kV
500
18 kA @ 15.0 kV; 23 kA @ 11.5 kV
750
28 kA @ 15.0 kV; 36 kA @ 11.5 kV
37 kA @ 15.0 kV; 48 kA @ 11.5 kV
21 kA @ 38.0 kV; 35 kA @ 23.0 kV
Rated short-circuit current
kA
31.5
40
50
63
40
20
25
31.5
40
50
63
20
25
31.5
40
20
25
20
25
31.5
40
Vacuum
interrupter type
VS-17006
VS-17040
VS-15052
VS-15052
VS-17006
VS-15052
VS-17040
VS-15052
VS-30030
Vacuum
interrupter type
VS-17006
31.5
VS-17040
VS-15052
40
VS-17040
50
VS-15052
63
VS-17085
VS-15052
40
VS-17040
20
VS-17006
25
VS-17006
VS-17006
31.5
VS-17040
VS-15052
40
VS-17040
50
VS-15052
63
VS-17085
20
VS-25008
25
VS-25008
31.5
VS-15052
40
VS-15052
20
VS-25008
25
VS-25008
20
VS-30030
25
VS-30030
31.5
VS-30041
40
VS-30041
Right hand limit
Graph
of curve (refer to
Figure 21)
1
A
36
E
36
B
49
B
41
A
23
B
36
E
36
B
48
D
35
Right hand limit
Graph
of curve (refer to
Figure 21)
1
A
31.5
E
31.5
B
40
E
40
B
50
F
63
B
40
E
40
A
20
A
25
A
31.5
E
31.5
B
40
E
40
B
50
F
63
C
20
C
25
B
31.5
B
40
C
20
C
25
D
20
D
25
D
31.5
D
40
35