Siemens 3AH3 Instruction Manual page 40

Vacuum circuit breaker operator modules 4.16 kv to 38 kv

Advertisement

48.0
48.6
48.6
48.0
3AH vacuum circuit breaker operator
Figure 22: Circuit breaker pole assembly/vacuum-check mechanical/contact-resistance test
40
Item
48.0
48.6
Detach lever (48.6) and insulated
Step 1
Primary contact CLOSED position and
Step 2
Primary contact OPEN position (forced
Step 3
3AHc vacuum circuit breaker operator
As-found insulation and contact
resistance tests
As-found tests verify the integrity of the
circuit breaker insulation system. Megger*
or insulation resistance tests and contact-
resistance tests conducted on equipment
prior to installation provide a basis of future
comparison to detect changes in the
protection afforded by the insulation
system. A permanent record of periodic
as-found tests enables the maintenance
organization to determine when corrective
actions are required by watching for
significant deterioration in insulation
resistance, or increases in contact
resistance.
* Megger is a registered trademark of
Megger Group, Ltd.
Description
Insulating coupler
Lever
coupler (48.0)
insulated coupler disconnected
open by manual pressure)
Upper connector pad
Primary contact
resistance test
Lower connector pad
Insulation and contact-resistance test
equipment
In addition to the high-potential test
equipment capable of test voltages as listed
in Table 4, the following equipment is also
required:
AC high-potential tester with test voltage
of 1,500 volts, 60 Hz
Test equipment for contact-resistance
tests.
Step 2
48.0
48.0
48.6
Step 2
Step 1
Step 3
48.0
Operating
position

Advertisement

loading

This manual is also suitable for:

3ahc