Cabinet Base; External Ports Of The Pre-Fab. Module - Huawei FusionModule1000A40 Product Description

Prefabricated all-in-one data cente
Hide thumbs Also See for FusionModule1000A40:
Table of Contents

Advertisement

FusionModule1000A40 Prefabricated All-in-One
Data Center
Product Description (Advanced Configuration, 208
V)

3.1.5.6 Cabinet Base

Sliding bases are configured for 1200 mm deep cabinets. The sliding feature is not
configured for 1100 mm deep cabinets.
A cabinet base has the following features:
Figure 3-12 Cabinet sliding base
(1) Fixed leg

3.1.6 External Ports of the Pre-fab. Module

End connectors are used at the ports designed for routing power cables, optical
fibers, and network cables on the pre-fab. module exterior. All ports provide good
water tightness and thermal insulation performance, meeting equipment
compartment weather-tight requirements. Pipe feature an anti-backflow design,
adapting to different configuration demands. Fire extinguishing devices on the
pre-fab. module exterior meet sealing conditions.
Figure 3-13 External ports
Issue 03 (2021-02-10)
Cabinets are raised for 250 mm high and secured to bases, which are
anchored to the steel floor using self-drilling tapping screws.
To increase maintenance space, the cabinet needs to be slid. Sliding bases are
configured for 1200 mm deep cabinets. The 1200 mm deep cabinet sliding
base can be used to slide the cabinet frontward and backward for 200 mm.
To prevent cabinets from sliding during the transportation of the pre-fab.
module if sliding bases are configured, transport fasteners are installed at the
front and rear of the sliding bases. After the pre-fab. module is installed and
secured, the transport fasteners need to be removed.
Cabinet bases can be used for cabinets that are 1100 mm and 1200 mm deep.
The bases can be 1100 mm or 1200 mm deep.
Copyright © Huawei Technologies Co., Ltd.
(2) Sliding platform
3 Architecture
(3) Transport fastener
19