Technical Specifications - Huawei FusionModule1000A40 Product Description

Prefabricated all-in-one data cente
Hide thumbs Also See for FusionModule1000A40:
Table of Contents

Advertisement

FusionModule1000A40 Prefabricated All-in-One
Data Center
Product Description (Advanced Configuration, 208
V)
Item
Water supply
requirements
Drainage
requirements
Power distribution
requirements
Note: If certain conditions are not met, contact Huawei technical support.

3.3.2.3 Technical Specifications

Table 3-15 General specifications
Item
Cooling mode
Refrigerant
Air supply mode
Dimensions (H x W
x D)
Net weight
Environmental
protection
Issue 03 (2021-02-10)
Specifications
The inlet water pressure should be in the range of 0.1–
0.7 MPa (a reducing valve must be installed at the
humidifier water inlet if the inlet water pressure
exceeds 0.7 MPa), and the temperature should be in the
range of 1°C–40°C.
The wet film humidifier uses tap water and does not
require an additional water treatment device at the
water inlet. The water requirements are as follows:
● Non-freezing and nephelometric turbidity units
(NTU) < 3
● No visible substances
● 6.5 ≤ pH value ≤ 8.5
● Total hardness (in CaCO3) ≤ 450 mg/L
The distance between the top drainage of the water
pump and the cabinet installation floor should not
exceed 4 m.
Leakage circuit breakers are not recommended for the
main power route. If a leakage circuit breaker is
required by the customer or local regulations, select the
residual current circuit breaker (RCCB) that is
insensitive to single-phase DC pulsation and transient
impulse current.
Specifications
Air cooled
R410A
Horizontal flow
2000 mm x 300 mm x 1100 mm (cabinet dimensions)
275 kg
RoHS, REACH
Copyright © Huawei Technologies Co., Ltd.
3 Architecture
37