Mitsubishi Electric BDT CITY MULTI Installation And Pre-Commissioning Booklet page 61

Table of Contents

Advertisement

[5-1 Dipswitch Functions and Factory Settings ]
(2) Additional dipswitch settings at time of shipment
Switch
SW4
1-10
SW6-10:
1:ON, 0:OFF
OFF
No.769
1000000011
No.832
0000001011
No.848
0000101011
No.896
0000000111
No.897
1000000111
No.900
0010000111
No.912
0000100111
No.913
1000100111
No.915
1100100111
No.916
0010100111
SW4
1-10 
No.918
0110100111
[0:OFF,
1:ON]
(Note 1)
No.921
1001100111
SW6-10:ON
No.922
0101100111
No.932
0010010111
No.933
1010010111
No.934
0110010111
No.964
0010001111
No.972
0011001111
No.982
0110101111
No.988
0011101111
Function according to switch setting
Function
OFF (LED3 Unlit)
Refer to the following page(s). [9 LED Status
Self-diagnosis/operation
Indicators on the Outdoor Unit Circuit
monitor
Board](page 281)
Test run mode: ON/OFF
Stops all ICs
Cumulative compressor
Retained
operation time deletion
On-cycle defrost function
Disabled
OC
Retained (IC/OC)
Clearance of error
history
OS
Retained (OS)
High sensible heat opera-
Depends on the combined setting with No.
tion setting
900 (Note 4)
High sensible heat opera-
Depends on the combined setting with No.
tion setting
897 (Note 4)
Pump down function
Normal control
Forced defrost (Note 3)
Normal control
EP200 - EP350:
Defrost start temperature
-13°C [9°F]EP400 -
(Note 3)
EP500:-11°C [12°F]
EP200 - EP250:
Defrost end temperature
10°C [50°F]EP300 -
(Note 3)
EP500:7°C [45°F]
Changes the defrost timer
50 minutes
setting (Note 3)
Temperature unit display
°C
Refrigerant amount adjust-
Normal control
ment
Heating backup
Disabled
Effective only when
TH7 ≤ 5 is true or the
Snow sensor setting
snow sensor contact
input is on.
Continuous fan op-
Snow sensor setting
eration (FAN=50%)
Target evaporation tem-
Depends on the setting combination with No.
perature setting
982 (Note 5)
Automatic cooling/heating
mode (IC with the smallest
Normal control
address)
Target evaporation tem-
Depends on the setting combination with No.
perature setting
964 (Note 5)
Refrigerant recovery/Evac-
uation (two-way valve/
Disabled
LEV1 open)
Switch setting timing
ON (LED3 Lit)
Anytime after power on
Sends a test-run sig-
Anytime after power on
nal to all IC
Any time after being energized (When
Cleared
changed from OFF to ON)
After being energized and while the com-
Enabled
pressor is stopped
Deleted (IC/OC)
Anytime after power on (OFF→ON)
Deleted (OS)
After being energized and while the com-
pressor is stopped
After being energized and while the com-
pressor is stopped
Pump down opera-
After being energized and while the com-
tion
pressor is stopped
10 minutes after the completion of de-
Forced defrost starts
frost operation (OFF→ON) or 10 minutes
after compressor start-up (OFF→ON)
-8°C [18°F]
Anytime after power on
5°C [41°F]
Anytime after power on
90 minutes
Anytime after power on (OFF→ON)
°F
Anytime after power on
Anytime after power on (except during
Refrigerant amount
initial startup/becomes ineffective 60
adjust mode
minutes after compressor started up.
Enabled
Anytime after power on
Effective when TH7
Anytime after power on
≤ 5 is true
Intermittent fan op-
eration (The fan op-
erates in the cycle of
being in operation at
100% capacity for 5
Anytime after power on
minutes and then
stops and remains
stopped for 30 min-
utes.)
Anytime after power on
Automatic cooling/
Before power on (After configuring the
heating mode
setting, perform a power reset.)
Anytime after power on
After being energized and when units are
Enabled
stopped
Units that
require
switch
setting
(Note 2)
C
A
C
B
C
A
A
A
D
B
B
B
C
A
A
C
C
A
A
A
C
61