OUTDOOR UNIT SPACING S SERIES
4. Outdoor Installation
4-2. Spacing
PUMY-P112, 125, 140YKM, VKM's external dimension. (Fig.4-2-1)
Fig. 4-2-1 PUMY-P-YKM, VKM dimension
4-2-1. Spacing individual PUMY-P-YKM, VKM
Follow Fig. 4-2-2 ~ 7 to space individual PUMY-P-YKM, VKM at the installation site.
Fig. 4-2-2
Obstacles at rear only
Fig. 4-2-4
Obstacles at rear and sides only
* Using an optional air outlet guide, the
clearance >= 500 mm [19-11/16"].
Fig. 4-2-6
Obstacles at front and rear only
26
4-2-2. Spacing grouped PUMY-P-YKM, VKM
Follow Fig. 4-2-8 ~ 13 to space grouped PUMY-P-YKM, VKM at the installation site.
Leave 10 mm [13/32"] space or more between PUMY-P-YKM, VKM units.
m
m
i [
] . n
Fig. 4-2-3
Obstacles at rear and above only
* Using an optional air outlet guide, the
* Using an optional air outlet guide, the
clearance >= 500 mm [19-11/16"].
clearance >= 1000 mm [39-3/8"].
Fig. 4-2-5
Obstacles at front only
1500
[59-1/16"]
500
[19-11/16"]
* NO upward airflow outlet guide.
* Using an optional air outlet guide for upward
airflow, the clearance >= 1500 mm [59-1/16"].
Fig. 4-2-7
Obstacles at rear, sides and above only
SYSTEM DESIGN
PUMY-P-YKM, VKM can connect Indoor unit sized P15 to
P140; and can connect totally 1-12 Indoor units with total
capacity ranged 50%-130% of the outdoor unit capacity.
Connectable Indoor capacity
PUMY-P112YKM
P56-P145
PUMY-P125YKM
P63-P162
PUMY-P140YKM
P70-P182
Connectable Indoor capacity
PUMY-P112VKM
P56-P145
PUMY-P125VKM
P63-P162
PUMY-P140VKM
P70-P182
* In case of side-by-side installation, <=3 units;
* When using an optional air outlet guide,
* Do not install the optional air outlet guides
the clearance is 1000 mm [39-3/8"] or more.
for upward airflow.
Fig. 4-2-8
Fig. 4-2-9
Obstacles at rear or front only
Obstacles at rear and above only
* Using an optional air outlet guide, the
clearance >= 1000 mm [39-3/8"].
Fig. 4-2-10
Fig. 4-2-11
Obstacles at front and rear only
Parallel individuals arrangement
* Stacked layer <= 2 units;
* Side-by-side stacked groups <= 2 groups.
Fig. 4-2-12
Fig. 4-2-13
Parallel groups arrangement
Stacked groups arrangement
G10 2nd
Connectable Indoor unit
P15-P125, 1-9 units
P15-P140, 1-10 units
P15-P140, 1-12 units
Connectable Indoor unit
P15-P125, 1-9 units
P15-P140, 1-10 units
P15-P140, 1-12 units
m
m
i [
] . n
4 - 31