Huawei NetCol5000-C065 Quick Manual page 4

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C065:

Advertisement

Installing Cabinets Side by Side
3.5
3.6
Securing the Equipment
Front
Rear
4
Installing Pipes
4.1
Pipe Layout
1. A 1:100 tilt should be reserved for the main drainpipe and humidifier water inlet pipe.
2. Keep a clearance of at least 25 mm between pipes. Secure the pipes to supports every a
certain distance.
3. Clean the water inlet engineering pipes to avoid impurities entering into the humidifier.
4. A reducing valve must be installed if the inlet water pressure exceeds 0.7 MPa.
5. Pipes should be wrapped with thermal insulation foam along the route.
Unit: mm