Download Print this page

Siemens 24RFDC/SET Manual page 12

Radio set with 7-day room temperature controller

Advertisement

Mounting and
installation of
receiver
RCR10/868
Commissioning
1. REV24RF../SET
2. Switch on the
REV24RF..
3. Temporarily mount
the RCR10/868
4. Test radio link /
Identify best RF
reception location
LED_1
LED_2
12 / 18
Siemens
Building Technologies
Make sure the receiver is not connected to power during wiring!
Reconnect the unit to power only after the unit is fully mounted.
· During installation, attach first and wire the unit rear without cover (L/N = mains 230
VAC, LX/L1 = consumer). Slide in the cover from above, swing downward and secure
with a screw in the upper portion of the housing.
· For more detailed information, see the installation instructions supplied with the unit.
· Comply with all local regulations on electrical installations.
Warning!
No internal line protection for supply lines to external consumers.
Risk of fire and injury due to short-circuits!
· Adapt the line diameters as per local regulations to the rated value of the installed
overcurrent protection device.
· The AC 230 V mains supply line must have an external circuit breaker with a rated
current of no more than 10 A.
·
The room unit and receiver are interconnected at the factory in the RF/SET. As a result,
you do not need to manually connect the two units.
However, you can still manually connect the room unit and the receiver as needed.
See Point "7. Manually connect REV24RF.. and RCR10/868".
·
Remove the black transit tabs; the unit starts to operate as soon as you remove the
transit tabs on the battery contact. : Select desired language by
Confirm by
.
·
If possible, mount the receiver temporarily (e.g. using dual-sided adhesive tape) to try
to identify the best possible location for RF reception. To do this, fully wire the
RCR10/868 and close the front cover.
·
See Point "4 Test radio link / identify best RF reception location".
a) Switch on RCR10/868
b) Press the Test button on the rear or the REV24RF.. and place the unit in the best RF
reception location. Test the radio link between the room controller and all connected
receivers. On the RCR10/868, LED_2 flashes quickly.
The test turns off automatically after 10
pressing one of the following buttons :
c) The REV24RF.. shows the quality of the radio link to the connected RCR10/868. If
more than one receiver is connected to the same REV24RF.., the display changes
every 10 seconds from RCR 01 to RCR 02, etc..
Select the receiver with
1 minute.
d) REV24RF..: The greater the visible bar under numbers 0...9, the better the radio link.
If the bar is below the number 0, radio link is not guaranteed. In this case, move the
room controller to a different location and shorten the distance between
REV24RF.. and RCR10/868.
Repeat the test until quality is sufficient.
Insufficient
Sufficient
Room temperature controller radio set REV24RF../SET
minutes or you can manually end it by
,
or
or
. The selected receiver is tested continuously for
Good
or
.
.
the
Very good
CE1N2206en
2018-11-07

Advertisement

loading

This manual is also suitable for:

Rev24rf set seriesRev24rf seriesRev24rfdc/set