Download Print this page

ABB IRP Instruction Leaflet

Directional overcurrent ground relays

Advertisement

Quick Links

Effective: October 1999
Supersedes I.L. 41-133R, Dated August 1998
( )
Denotes Changed Since Previous Issue
!
CAUTION
Before putting relays into service, remove all
blocking which may have been inserted for the
purpose of securing the parts during shipment,
make sure that all moving parts operate freely,
inspect the contacts to see that they are clean
and close properly, and operate the relay to
check the settings and electrical connections.
1.0 APPLICATION
These relays are ground directional overcurrent
relays which are used for the protection of transmis-
sion lines and feeder circuits. Both the time overcur-
rent
and
instantaneous
directionally controlled.
The type IRP relay is potential polarized. The type
IRC relay is current polarized. The type IRD relay is a
dual polarized relay which can be polarized from a
potential source, from a local ground source or from
both simultaneously.
2.0 CONSTRUCTION AND OPERATION
The various types of relays consist of a directional
unit or units (D), an auxiliary switch (CS-1 or a tele-
phone relay TR-1), a time-overcurrent unit (CO), an
instantaneous overcurrent unit (I), an instantaneous
overcurrent unit transformer, and two indicating con-
tactor switches (ICS/I) and (ICS/T). The principle
component parts of the relays and their locations are
shown in Figures 1 through 6, starting on page 19.
2.1 TIME-OVERCURRENT UNIT (CO)
The electromagnets for the types IR-5, IR-6, IR-7,
All possible contingencies which may arise during installation, operation or maintenance, and all details and
variations of this equipment do not purport to be covered by these instructions. If further information is desired
by purchaser regarding this particular installation, operation or maintenance of this equipment, the local ABB
Power T&D Company Inc. representative should be contacted.
Printed in U.S.A.
ABB Automation Inc.
Substation Automation and Protection Division
Coral Springs, FL 33065
overcurrent
units
are
Types IRP, IRC and IRD
Directional Overcurrent
Ground Relays
IR-8 and IR-9 relays have a main tapped coil located
on the center leg of an "E" type laminated structure
that produces a flux which divides and returns
through the outer legs. A shading coil causes the flux
through the left leg to lag the main pole flux. The
out-of-phase fluxes thus produced in the air gap
cause a contact closing torque.
The electromagnet for the type IR-2 and IR-11 relays
has a main coil consisting of a tapped primary wind-
ing and a secondary winding. Two identical coils on
the outer legs of the lamination structure are con-
nected to the main coil secondary in a manner so that
the combination of all the fluxes produced by the
electromagnet result in out-of-phase fluxes in the air
gap. The out-of-phase air gap fluxes produced cause
a contact closing torque.
The dc indicating contactor switch is a small clapper
type device. A magnetic armature, to which
leaf-spring mounted contacts are attached, is
attracted to the magnetic core upon energization of
the switch. When the switch closes the moving con-
tacts bridge two stationary contacts, completing the
trip circuit. Also during this operation two fingers on
the armature deflect a spring located on the front of
the switch, which allows the operation indicator target
to drop.
The front spring, in addition to holding the target, pro-
vides restraint for the armature and thus controls the
pickup value of the switch.
2.2 DIRECTIONAL UNIT (D)
The directional unit is a product induction cylinder
type unit operating on the interaction between the
polarizing circuit flux and the operating circuit flux.
Mechanically, the directional unit is composed of four
basic components: A die-cast aluminum frame; an
Instruction Leaflet
41-133S

Advertisement

loading

Summary of Contents for ABB IRP

  • Page 1 If further information is desired by purchaser regarding this particular installation, operation or maintenance of this equipment, the local ABB Power T&D Company Inc. representative should be contacted.
  • Page 2 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD electromagnet; a moving assembly; and a molded The TR-1 switch is a telephone relay. A tapped resis- bridge. tor is used to enable one to use the auxiliary switch on a 24, 48, 125 or 250 volt dc system connected per The frame serves as the mounting structure for the Figure 26, page 40.
  • Page 3 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD 3.0 CHARACTERISTICS 4.0 TIME CURVES The times curves for the IRD relay are shown in Fig- The time characteristics of the directional overcurrent ures 23 (page 38) and 24 (page 38). Figure 23 con-...
  • Page 4 4.5 TYPE IRP RELAY ) 23.1 ------------------------- - 1850 The IRP relay is designed for potential polarization 0.25 and has its maximum torque when the current lags Entering Figure 23, (page 38) the directional unit the voltage by approximately 60 degrees. The shift-...
  • Page 5 5.2 INSTANTANEOUS RECLOSING IRC relay and a directional unit and phase-shifting The factory adjustment of the CO unit contacts circuit similar to those in the IRP relay. provides a contact follow. Where circuit breaker The current-polarized directional unit of the IRD relay...
  • Page 6: Installation

    41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD 6.0 INSTALLATION 2. Reverse the leads to switch jaw terminals 6 and 7. For the IRD, also reverse leads to switch jaw terminals 4 and 5. The relays should be mounted on switchboard pan- els or their equivalent in a location free from dirt, 3.
  • Page 7: Routine Maintenance

    41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD checked by inserting the tap screw in the desired 7.1.4 Indicating Contactor Switches (ICS/I) and (ICS/T) tap hole and applying rated tap value current. The contact should close within 5% of tap value a.
  • Page 8 7.4.1 Directional Unit (D) when the relay is energized on current or voltage In the type IRP and IRC relays the directional unit is alone. the lower cylinder unit. In the type IRD the directional The reversing of the spurious torques is accom- units are the lower and middle cylinder units.
  • Page 9 Apply 120V AC to terminals 4 (+) and 5 for IRD out until the proper operating time has been and terminals 6 (+) and 7 for IRP and adjust core obtained. so that contacts just open.
  • Page 10: Renewal Parts

    41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD tion indicator target should drop freely bringing the clearance for 3/64” by means of the two small nuts letter “I” into view. on either side of the Micarta disc. The TR-1 switch does not require adjustment.
  • Page 11 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD TABLE † DIRECTIONAL UNIT CALIBRATION RELAY CURRENT BOTH PLUGS IN CONDITION ADJUSTMENT RATING AMPERES 0.5-2.5 Amps Right (front-view) plug 5 - 80 screwed out until 2-6 Amps Spurious Torque is Spurious Torque in contact reversed.
  • Page 12 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD RATINGS OF OVERCURRENT UNIT RANGE CONTINUOUS RATING ONE SECOND RATING † (AMPERES) (AMPERES) .5-2 4-16 10-40 20-80 Thermal capacities for short times other than one second may be calculated on the basis of time being †...
  • Page 13 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD ENERGY REQUIREMENTS – 60 HERTZ DIRECTIONAL UNIT OPERATING CIRCUIT BURDEN VOLT AMPERES At 3 Times At 10 Times At 20 Times Power Continuous One Second Minimum Minimum Minimum Minimum †...
  • Page 14: Energy Requirements

    41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD ENERGY REQUIREMENTS TIME OVERCURRENT UNITS: TYPE IRD-2, IRC-2, IRP-2, ‡ VOLT AMPERES At 3 Times At 10 Times At 20 Times Power Continuous One Second Minimum Minimum Minimum Minimum †...
  • Page 15 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD ENERGY REQUIREMENTS TIME OVERCURRENT UNITS: IRD-5, IRC-5, IRP-5 IRD-6, IRC-6, IRP-6 ‡ VOLT AMPERES Power 3 Times 10 Times 20 Times Ampere Continuous One Second † Tap Value Tap Value...
  • Page 16 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD ENERGY REQUIREMENTS TIME OVERCURRENT UNITS: IRD-7, IRC-7, IRP-7 ‡ VOLT AMPERES Power 3 Times 10 Times 20 Times Ampere Continuous One Second † Tap Value Tap Value Rating Rating Tap Value...
  • Page 17 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD ENERGY REQUIREMENTS IRD-8, IRC-8, IRP-8 TIME OVERCURRENT UNITS: IRD-9, IRC-9, IRP-9 ‡ VOLT AMPERES Power 3 Times 10 Times 20 Times Ampere Continuous One Second † Factor Tap Value Rating...
  • Page 18 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD ENERGY REQUIREMENTS TIME OVERCURRENT UNITS: IRD-11, IRC-11, IRP-11 ‡ VOLT AMPERES Power 3 Times 10 Times 20 Times Ampere Continuous One Second † Factor Tap Value Rating Rating Tap Value...
  • Page 19 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD Sub 1 Sub 1 9664A15 9664A16 Photo Photo Figure 1: Type IRD Relay Without Case (Front View) Figure 2: Type IRD Relay without Case (Rear View) Instantaneous Overcurrent Unit and Saturating...
  • Page 20 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD 1) Stationary Contacts 2) Stationary Contact Pressure Spring 3) Magnetic Adjusting Plugs 4) Upper Bearing Screw 5) Moving Contact 6) Spring Adjuster Clamp 7) Current Bias Vane Photo Figure 3: Directional Unit.
  • Page 21 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD Instantaneous Overcurrent Unit Stationary Contact Moving Contact. Saturating Transformer Tap Block Photo Figure 5: Instantaneous Overcurrent Unit Photo Figure 6: Indicating contactor Switch (ICS)
  • Page 22 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD *Sub 9 184A033 Figure 7: internal Schematic of the Type IRP Relay in the Type FT-31 Case Denotes change since previous issue...
  • Page 23 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD *Sub 8 184A034 Figure 8: Internal Schematic of the Type IRC Relay in the Type FT-31 Case Denotes change since previous issue...
  • Page 24 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD *Sub 11 184A020 Figure 9: Internal Schematic of the Type IRD Relay in the Type FT-41 Case Denotes change since previous issue...
  • Page 25 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD *Sub 2 9654A57 Figure 10: Internal Schematic of the Type IRP Relay, with Field Modified Reversed “D” Contacts, in the Type FT-31 Case. Denotes change since previous issue...
  • Page 26 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD *Sub 2 9654A58 Figure 11: Internal Schematic of the Type IRC Relay, with Field Modified Reversed “D” Contacts, in the Type FT-31 Case Denotes change since previous issue...
  • Page 27 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD *Sub 2 9654A56 Figure 12: Internal Schematic of the Type IRD Relay, with Field Modified Reversed “D” Contacts, in the Type FT-41 Case Denotes change since previous issue...
  • Page 28 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD...
  • Page 29 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD...
  • Page 30 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD...
  • Page 31 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD *Sub 1 619584 Figure 16: Typical Time Curves of the Time-Overcurrent Unit of the Short Time (2) Relays Denotes change since previous issue...
  • Page 32 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD Sub 2 418245 Figure 17: Typical Time Curves of the Time-Overcurrent Unit of the Long Time (5) Relays...
  • Page 33 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD *Sub 3 418246 Figure 18: Typical Time Curve of the Time-Overcurrent Unit of the Definite Time (6) Relays Denotes change since previous issue...
  • Page 34 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD *Sub 3 418247 Figure 19: Typical Time Curve of the Time-Overcurrent Unit of the Definite Time (7) Relays. Denotes change since previous issue...
  • Page 35 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD Sub 3 418248 Figure 20: Typical Time Curve of the Time-Overcurrent Unit of the Definite Time (8) Relays.
  • Page 36 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD Sub 2 418249 Figure 21: Typical Time Curve of the Time-Overcurrent Unit of the Definite Time (9) Relays.
  • Page 37 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD Sub 2 288B655 Figure 22: Typical Time Curve of the Time-Overcurrent Unit of the Definite Time (11) Relays.
  • Page 38 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD *Sub 7 538108 Figure 23: Typical Operating Times For The Directional Unit Sub 2 538109 Figure 24: Typical Operating Times For the Instantaneous Overcurrent Unit Denotes change since previous issue...
  • Page 39 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD Sub 5 184A118 Figure 25: Diagram Of Test Connections Of The Time-Overcurrent Unit...
  • Page 40 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD Sub 4 184A316 Figure 26: Selection of Proper Voltage Tap for Auxiliary Switch Operation Sub 1 1518B95 Figure 27: Test Connections...
  • Page 41 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD NOTES...
  • Page 42 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD NOTES...
  • Page 43 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD...
  • Page 44 41-133S Directional Overcurrent Ground Relays Types IRP, IRC and IRD ABB Automation Inc. 4300 Coral Ridge Drive Coral Springs Florida 33065 TEL: 954-752-6700 FAX: 954-345-5329 Printed in U.S.A. visit our website at www.abbus.com/papd...

This manual is also suitable for:

IrcIrd