INSTALLATION AND WIRING
BDS0029 rev 11
Cylon® FBXi
CAUTION - DANGER OF EXPLOSION IF BATTERY IS INCORRECTLY REPLACED.
REPLACE ONLY WITH THE SAME OR EQUIVALENT TYPE RECOMMENDED BY THE
MANUFACTURER. DISPOSE OF USED BATTERIES ACCORDING TO THE MANUFACTURER'S
INSTRUCTIONS.
Supply Requirements
Supply
Rating
FLX Power Connection
©ABB 2021 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
24 V AC ±20 % 50/60 Hz
FBXi
20 VA (no FLX modules)
FBXi + 1 x FLX
32 VA
FBXi + 2 x FLX
44 VA
|
|
FBXi + 16 x FLX
68 VA
Proprietary FLX bus connector
carries power and comms from
FBXi unit. FBXi-X256 can supply
power to up to 4 FLX modules.
Ground
Common
1

Advertisement

loading

Summary of Contents for ABB Cylon FBXi

  • Page 1 FBXi + 16 x FLX 68 VA Proprietary FLX bus connector FLX Power Connection carries power and comms from FBXi unit. FBXi-X256 can supply power to up to 4 FLX modules. ©ABB 2021 All Rights Reserved. Subject to change without notice WWW.CYLON.COM...
  • Page 2 Klemm-nummer Power 24 V AC/DC 93, 94 Important: The common power connection (terminal 33) must be connected to Earth. ABB Cylon recommend that this is done at the 24 V AC transformer. 95, 96 RS-485 Port 1 (BACnet® MS/TP or Modbus RTU) screw terminal MS/TP subnet terminator switch is located beside the port.