Siemens 3AD8 Instruction Manual page 12

Remote control unit (rcu)
Hide thumbs Also See for 3AD8:

Advertisement

Table 6: Radio power supply settings
Name
Range/choice
Radio/modem power
supply
Controlled supply
Radio supply voltage
Radio average current
Radio reset time
Table 7: Radio/modem serial interface settings
Name
Range/choice
RS232 signals
Radio data interface
Logic level signal
type
Radio signal voltage
PTT enabled
PTT pre-transmit time
PTT post-transmit time
TTL Tx polarity
Normal/inverted
TTL Rx polarity
Normal/inverted
1,200, 2,400,
4,800, 9.600,
Data rate
19,200, 38,400,
57,600, 115,200
CTS handshaking
Enabled/disabled
support
RTS handshaking
Enabled/disabled
support
Data bits
Stop bits
Parity enabled
Enabled/disabled
Parity
12
Radio power supply settings
Unit
Off
Battery
3,000-9,000
mV
10-1,000
mA
10
1-255
minutes
Radio/modem serial interface settings
Unit
(3-9 V)
3,000-9,000
mV
On/off
0-100
100 ms
0-100
100 ms
bps
8 bits
Bits
1 or 2
Bits
Odd or even
Default
Sets the power source for the radio or modem.
Off - no power supply.
Off
Battery - power supply from the battery via a relay.
Controlled supply - a voltage controlled supply is provided.
6,000 mV
Voltage when using controlled supply.
Enter the average current the installed radio will consume. This is
required for reliable battery management when running from auxiliary
100 mA
power supply.
This value is an estimate of: the receive current plus the transmit current
x transmit duty cycle. Required accuracy is +/- 50%.
This is a time-out setting in multiples of 10 minutes. If a protocol
message has not been received for this time, then the radio will be
2,550
powered off for 10 seconds and then powered on again. The purpose is
minutes
to restart the radio periodically if there is no SCADA activity just in case
the radio is the problem. Range is 1 to 255 giving 10 to 2,550 minutes.
Default
Signals can be RS232 or logic level when logic level, voltage and Tx/Rx
RS232
signal polarity can be configured.
5,000
This sets the radio signal voltage when using logic-level serial interface.
Off
To enable PTT with pre-transmit and post-transmit times as below.
0
PTT output will be turned on for this time period before transmitting.
PTT output will remain on for this time period after transmitting has
0
stopped.
Normal TTL Tx polarity will have a logic high when idle. Start, stop and
Normal
data bits will have standard polarity. Inverted TTL Tx polarity will have a
logic low when idle. Start, stop and data bits will be inverted also.
Normal TTL Rx polarity will have a logic high when idle. Start, stop and
Normal
data bits will have standard polarity. Inverted TTL Rx polarity will have a
logic low when idle. Start, stop and data bits will be inverted also.
115,200
When enabled, RCU serial transmission will only occur when the CTS
Disabled
input pin is asserted. When disabled, the CTS input pin is ignored.
When enabled, the RCU RTS output pin will be de-asserted in request to
Disabled
stop receiving serial data (buffer full, unable to process more incoming
data). When disabled, the RTS output pin is de-asserted.
8 bits
1
Disabled
Odd
Description/comment
Description/comment