Siemens 3AD8 Instruction Manual page 28

Remote control unit (rcu)
Hide thumbs Also See for 3AD8:

Advertisement

D_PID
Phase
Fusesaver - Remote protection bit -
instantaneous
Source: Fusesaver
122
A
123
B
States: ‒/remote protection bit
124
C
instantaneous
Event time tag: Remote control unit (RCU)
time
Fusesaver - Remote protection bit - no
reclose
125
A
Source: Fusesaver
126
B
127
C
States: ‒/remote protection bit no reclose
Event time tag: RCU time
Fusesaver - In force protection bit -
protection off
128
A
Source: Fusesaver
129
B
States: ‒/protection bit in force protection
130
C
off
Event time tag: RCU time
Fusesaver - In force protection bit -
instantaneous
131
A
Source: Fusesaver
132
B
States: ‒/protection bit in force
133
C
instantaneous
Event time tag: RCU time
Fusesaver - In force protection bit - no
reclose
134
A
Source: Fusesaver
135
B
136
C
States: ‒/protection bit in force no reclose
Event time tag: RCU time
RCU - Excessive cleared faults
Source: RCU
137
States: Cleared faults excessive/clear faults
not excessive
Event time tag: RCU time
RCU - Primary test mode
Source: RCU
138
States: In/out
Event time tag: RCU time
28
RCU database digital points list
Name/states/source
Status/events/restart/qualifiers
State: Set when Fusesaver remote protection bit instantaneous mode is set.
Cleared when Fusesaver remote protection bit instantaneous is cleared. This
status data comes from the Fusesaver live-data stream.
Events: Events generated by change of state above.
On restart: Volatile - state clear on restart.
Data qualifiers: Override, online, restart, communications lost.
State: Set when Fusesaver remote protection bit no reclose mode is set. Cleared
when Fusesaver remote protection bit no reclose is cleared. This status data
comes from the Fusesaver live-data stream.
Events: Events generated by change of state above.
On restart: Volatile - state set on restart.
Data qualifiers: Override, online, restart, communications lost.
State: Set when Fusesaver in force protection bits have protection off set.
Cleared when Fusesaver in force protection bits have protection off cleared. This
status data comes from the Fusesaver live-data stream.
Events: Events generated by change of state above.
On restart: Volatile - state set on restart.
Data qualifiers: Override, online, restart, communications lost.
State: Set when Fusesaver in force protection bits have instantaneous set.
Cleared when Fusesaver in force protection bits have instantaneous cleared.
This status data comes from the Fusesaver live-data stream.
Events: Events generated by change of state above.
On restart: Volatile - state set on restart.
Data qualifiers: Override, online, restart, communications lost.
State: Set when Fusesaver in force protection bits have no reclose set. Cleared
when Fusesaver in force protection bits have no reclose cleared. This status data
comes from the Fusesaver live-data stream.
Events: Events generated by change of state above.
On restart: Volatile - state set on restart.
Data qualifiers: Override, online, restart, communications lost.
State: Set when the RCU processes a specified number of cleared fault events
within a specified sliding time window. State is cleared by protection flag reset
timer or by operator control.
Events: Set event generated when a specified number of cleared fault events
have been generated by the Fusesaver within the specified sliding time window.
Cleared event generated when state is cleared as above.
On restart: Volatile - state clear on restart.
Data qualifiers: Override.
State: Controlled by C_PID 18 which can set or clear the point. When set, the
RCU primary test mode is in. When clear, the RCU primary test mode is out.
Events: Events generated by change of state above.
On restart: Volatile - state clear on restart.
Data qualifiers: Override.