Advertisement

Digital points
Table 15: RCU database digital points list
D_PID
Phase
RCU - Door open
Source: Remote control unit (RCU)
0
States: Open/closed
Event time tag: RCU time
RCU - Remote control on/off
Source: RCU
1
States: On/off
Event time tag: RCU time
RCU - Battery needs to be replaced
Source: RCU
2
States: Needs to be replaced/OK
Event time tag: RCU time
RCU - Source power on
Source: RCU
3
States: Has power source/no power source
Event time tag: RCU time
RCU - Solar panel problem
Source: RCU
4
States: Solar panel OK/solar panel problem
Event time tag: RCU time
RCU - Configuration error
Source: Fusesavers all phases
5
States: OK/configuration error
Event time tag: RCU time
Fusesaver unaccessible
Source: Fusesavers all phases
6
States: Unaccessible/accessible
Event time tag: RCU time
20
RCU database digital points list
Name/states/source
Status/events/restart/qualifiers
State: Set when the door is open. Cleared when the door is closed.
Events: Events generated by change of state above.
On restart: Volatile - state updated on restart. No event generated when state
is updated on restart.
Data qualifiers: Override.
State: Set when remote control switch on front panel is on. Cleared when
remote control switch on front panel is off.
Events: Events generated by change of state above.
On restart: Volatile - state updated on restart. No event generated when state
is updated on restart.
Data qualifiers: Override.
State: Set when RCU battery needs to be replaced. Cleared when RCU battery is
replaced.
Events: Events generated by change of state above.
On restart: Non-volatile - This state is non-volatile and is carried through a
restart.
Data qualifiers: Override.
State: Set when RCU has a power source (auxiliary supply or solar). Cleared
when the RCU has no power source.
Events: Events generated by change of state above.
On restart: Volatile - state updated on restart.
Data qualifiers: Override.
State: Set when RCU is configured for solar operation and detects that the solar
panel has not been supplying any voltage or has not been able to fully recharge
the battery over a period of several days. Cleared when the solar panel does
recharge battery or on RCU restart.
Events: Events generated by change of state above.
On restart: Volatile - state clear on restart.
Data qualifiers: Override.
State: Set when there is a configuration error, which means there is a
discrepancy between the configuration loaded into the RCU and Fusesaver on
the line. Cleared when a valid configuration is detected.
Events: Events generated by change of state above.
On restart: Volatile - state clear on restart.
Data qualifiers: Override, restart.
State: Set when the RCU is unable to access Fusesavers due to a Siemens
Connect user on site having established an operating session with the
Fusesavers. In this case, the RCU can report data but cannot make controls or
retrieve events. This means that events will be delayed for the duration of the
Siemens Connect session (but will still have the correct time tag when they are
retrieved). Cleared when Siemens Connect session finishes.
Events: Events generated by change of state above.
On restart: Volatile - state clear on restart.
Data qualifiers: Override.