Analog points
Table 16: RCU database analog points list
Name/source/engineering units/
A_PID
Phase
RCU - Battery life remaining
Source: Remote control unit (RCU)
Engineering unit: Days
0
Range: 0-4,000
Resolution: 1
Event time tag: RCU time
RCU - Protocol messages received
without error
Source: RCU
Engineering unit: Numerical count
1
Range: 0-65,535
Resolution: 1
Event time tag: No events
RCU - Protocol messages received with
errors
Source: RCU
Engineering unit: Numerical count
2
Range: 0-65,535
Resolution: 1
Event time tag: No events
RCU - Protocol messages sent
Source: RCU
Engineering unit: Numerical count
3
Range: 0-65,535
Resolution: 1
Event time tag: No events
RCU - Restart count
Source: RCU
Engineering unit: Numerical count
4
Range: 0-65,535
Resolution: 1
Event time tag: No events
Communications module - Battery life
remaining
Source: Communications module
5
A
Engineering unit: Percentage
6
B
7
C
Range: 0-100%
Resolution: 1%
Event time tag: RCU time
30
RCU database analog points list
resolution/time tag
Value/events/restart/qualifiers
Value: Battery life remaining in days until it needs to be replaced.
Events and deadbands: Deadband of 1 day.
On restart: Non-volatile data, carried through restart.
Data qualifiers: Override.
Value: Current number of protocol messages received without error.
Events and deadbands: No events generated (and therefore no deadbands).
On restart: Restart to 0 on a restart.
Data qualifiers: Override.
Value: Current number of protocol messages received with error.
Events and deadbands: No events generated (and therefore no deadbands).
On restart: Restart to 0 on a restart.
Data qualifiers: Override.
Value: Current number of protocol messages sent.
Events and deadbands: No events generated (and therefore no deadbands).
On restart: Restart to 0 on a restart.
Data qualifiers: Override.
Value: Increments each time RCU microprocessor restarts.
Events and deadbands: No events generated (and therefore no deadbands).
On restart: Non-volatile data, carried through restart.
Data qualifiers: Override.
Value: Last record of battery life remaining reported by the communications
module.
Events and deadbands: Deadband of 1%.
On restart: Point is set to 0.
Data qualifiers: Override, online, restart, communications lost.