Siemens 3AD8 Instruction Manual page 26

Remote control unit (rcu)
Hide thumbs Also See for 3AD8:

Advertisement

D_PID
Phase
Fusesaver - In force protection mode -
normal single
Source: Fusesaver
98
A
99
B
States: ‒/protection mode in force normal
100
C
single
Event time tag: Remote control unit (RCU)
time
RCU - Remote control enabled
Source: RCU
101
States: Disabled/enabled
Event time tag: RCU time
RCU - Remote control panel on
Source: RCU
102
States: On/off
Event time tag: RCU time
RCU - Sending phase control
103
A
Source: RCU
104
B
States: Sending control/not sending control
105
C
Event time tag: RCU time
RCU - Sending line control
Source: RCU
106
States: Control in progress/control not in
progress
Event time tag: RCU time
RCU - Fusesaver control panel controls
enabled
Source: RCU
107
A
108
B
States: Fusesaver control panel controls
109
C
enabled/Fusesaver control panel controls
disabled
Event time tag: RCU time
26
RCU database digital points list
Name/states/source
Status/events/restart/qualifiers
State: Set when Fusesaver in force protection mode is set to normal single.
Cleared when Fusesaver in force protection mode is set to normal, fast, fast
single or off. This status data comes from the Fusesaver live-data stream.
Events: Events generated by change of state above.
On restart: Volatile - state clear on restart.
Data qualifiers: Override, online, restart, communications lost.
State: Set when remote controls to the Fusesavers are enabled. Cleared when
remote controls to the Fusesavers are disabled. Remote controls are disabled if
the remote control switch is off, if any Fusesaver has its lever down, if Siemens
Connect is in session with any Fusesaver or if the RCU is updating new time to
the Fusesavers.
Events: Events generated by change of state above.
On restart: Volatile - state updated on restart.
Data qualifiers: Override.
State: Set when the Fusesaver control panel is on. Cleared when the Fusesaver
control panel is off. The Fusesaver control panel may be switched on by pressing
the on/off switch, it may be switched off with the on/off switch or by closing the
RCU door.
Events: Events generated by change of state above.
On restart: Volatile - state updated on restart.
Data qualifiers: Override, online.
State: Set when the RCU is in the process of sending a control to a specific
phase Fusesaver. Cleared when the RCU is not sending a control to a specific
phase Fusesaver.
Events: Events generated by change of state above.
On restart: Volatile - state updated on restart.
Data qualifiers: Override, online.
State: Set when the RCU is in the process of sending a control to all the
Fusesaver phases configured in the line. Cleared when the RCU is not sending a
control to all Fusesaver phases configured in the line.
Events: Events generated by change of state above.
On restart: Volatile - state updated on restart.
Data qualifiers: Override, online.
State: Set when the Fusesaver control panel controls are enabled for a specific
phase in a line. Cleared when the Fusesaver control panel controls are not
enabled for a specific phase in a line.
Phase controls are enabled when Fusesaver control panel controls are allowed
(refer to item 111 on page 27) and the enable control button has been pressed
(if present).
The phase controls can be disabled by pressing the enable control button, by
time-out or when Fusesaver control panel controls are not allowed (refer to item
111 on page 27).
If the panel type is one which does not have enable controls button, then the
button is assumed to be on.
Events: Events generated by change of state above.
On restart: Volatile - state updated on restart.
Data qualifiers: Override, online.