Degree of protection
Weight
Fig.4-1:
Degree of protection and weight
Nominal input voltage
Input voltage range
Emitted interference and surge immunity
Power consumption at U
N
Input fuse
Voltage rise of the supply voltage when
switching on
Voltage drop of the supply voltage when
switching off
Switch-on threshold
Switch-off threshold
Maximum power consumption
The UPS requires a maximum of 60 W (24 V, 2.5 A) from the 24 VDC
supply.
Fig.4-2:
+24V input voltage
Nominal input voltage
Input voltage range
Input frequency
Power consumption at U
N
Recommended protection
Fig.4-3:
115/230 VAC input voltage
Nominal output voltage
Output voltage range
Current output at U
N
Switching time
Electric Drives
| Bosch Rexroth AG
and Controls
IP 20
1 kg
24 VDC
24 VDC +20 %, -15 %
Umax = 35 V (for t < 100 ms)
2.5 A max.
None
Max. 500 ms (0 V to UN)
Max. 500 ms (UN to 0V)
15.5 V ±5 %
20.2 V ±5 %
60 W
115/230 VAC
85 – 264 VAC
47 – 63 Hz
115 VAC = 1.00 A typ.
230 VAC = 0.60 A typ.
5 A
24 VDC
24 VDC +20 %, -15 %
2.5 A max.
< 1 ms
15/45
Technical Data