Fuses; Rotary Switch S1; General Information - Bosch Rexroth IndraControl VAU 01.1Z Manual

Hide thumbs Also See for Rexroth IndraControl VAU 01.1Z:
Table of Contents

Advertisement

Project Planning Manual | Rexroth IndraControl VAU 01.1Z
6.5

Fuses

DANGER
CAUTION
6.6

Rotary Switch S1

6.6.1

General Information

The UPS is provided with 3 fuses. The FKS fuse (4 A, 32 V) can be reached
via the front panel (F1 connection). Both SMD fuses are located on the board.
Refer to Fig. 6-12.
Fig.6-14:
Position of the two SMD fuses
Risk to damage the UPS due to short-circuits!
Disconnect the UPS from the power supplies, before opening the device to
check or change a fuse!
If required, unplug all connectors from the VAU.
Risk to damage the UPS by electrostatic discharges!
Comply with all ESD protection measures when a fuse is changed or checked!
Avoid electrostatic discharges!
With the rotary switch different UPS times can be set. By using the switch po‐
sition from 0 to 3 the UPS time can be changed in steps of one minute. The
UPS time is the time period in which the connected device is provided with
output voltage of the UPS - after switching off of the input voltage.
Electric Drives
| Bosch Rexroth AG
and Controls
Interfaces, Display and Operating Components
29/45

Advertisement

Table of Contents
loading

Table of Contents