Bosch Rexroth AG | Electric Drives
Technical Data
4.3

Ambient Conditions

4.4

Standards

4.4.1

Used Standards

Rexroth IndraControl VAU 01.1Z | Project Planning Manual
and Controls
Bridging time
Maximum output power in the buffer mode 60 W
Fig.4-4:
Output voltage
In operation
Surrounding air
+5 to +45 °C
temperature
Maximum tem‐
Temperature change up to 3°C
perature gradi‐
per minute
ent
Relative humid‐
Climatic class 3K3 according to
ity
EN 60721, condensation not per‐
missible.
80 % humidity max. for 25 °C
Air pressure
Up to 2,000 m above MSL ac‐
cording to DIN 60204
Mechanical
Maximum vibration
strength
Frequency range: 10 to 150 Hz
Excursion: 0.075 mm for 10 to 57
Hz
Acceleration: 1 g for 57 to 150 Hz
Test duration for each axis: 10
frequency cycles
Frequency sweep rate:
1 octave/min
According to EN 60068-2-6, test
Fc
Degree of pollu‐
2
tion
Fig.4-5:
Ambient Conditions
The system components of the VAU 01.1Z correspond to the following stand‐
ards:
Standard
EN 60 61000-6-4
EN 60 61000-6-2
EN 60664-1
EN 60950
Maximum 3 minutes
Storage / Transport
-20 °C to +60 °C
Temperature change up to 3°C
per minute
Climatic class 3K3 according to
EN 60721, condensation not per‐
missible.
80 % humidity max. for 25 °C
Up to 3000 m above MSL accord‐
ing to DIN 60204
Maximum shock:
15 g according to EN 60
068-2-27, no disturbance of the
function
2
Meaning
Generic standard, emitted interference (industrial environ‐
ment)
Generic standard, noise immunity (industrial environment)
Overvoltage category II
Clearances and creepage distances office (environment)
and power units