8.6
(Optional) Connecting the Low Temperature Component Cables
Low temperature component
power cable from the outdoor
unit to the indoor unit
Low temperature component
power cable to the outdoor unit
The figure shows the cable
routing of NetCol8000-A045.
Also connect L/N to another
outdoor unit if NetCol8000-
A090 or NetCol8000-A120 is
configured.
(1) Low temperature component
(Optional) Connecting the
8.7
Water Sensor
Water sensor cable
29
(Optional) Connecting the
8.8
T/H Sensors Outside Cabinets
1. Connect the T/H sensor cables.
The T/H sensors in the aisles should be
installed on the door frames of server
cabinets, and 1.5 m (33 U) away from
the ground. After the sensors are secured,
set the sensor addresses according to the
following table.
T/H sensor
outside the
cabinet