Download Print this page

Huawei NetCol8000-A045D Quick Manual page 44

Hide thumbs Also See for NetCol8000-A045D:

Advertisement

10.2
Startup Process
1. First startup flowchart
Start
Tap Start on the home screen.
After tapping Yes, check the barcode and
the verification code shown on the screen.
Open the Service Expert app.
Tap StartUp > Offline Activation on app.
Enter Bar code and Verification code,
and tap Generate PWD.
Enter the generated startup password on
the screen of smart cooling product.
Tap Enter. The screen goes to Wizard
Startup.
Refrigerant is fully charged?
No
Tap No on the Wizard Startup screen to
exit wizard startup.
Tap Start on the home screen and choose
Maint > Diagnostic Mode > Enter.
Set the compressor speed to 3000 rpm.
Charge the remaining amount of
refrigerant from the low-pressure needle
valve.
Choose Maint > Diagnostic Mode > Exit
and tap Shutdown on the home screen.
Choose Maint > Wizard Startup to enter
wizard startup.
Go to step 2.
2. Wizard startup flowchart
Start
Precautions & check items
Yes
Select commissioning items
Yes
Indoor fan commissioning
Success
Outdoor fan commissioning
Success
Electric heater commissioning
Success
Humidifier commissioning
Success
Cooling system commissioning
Success
End
Yes
Tap Yes on
the Wizard
Startup
screen to
enter
wizard
startup.
43
No
No
Commissi
Fail
oning
interrupte
d (Handle
Fail
the fault
by
referring
Fail
to the tips
displayed
on the
Fail
home
screen.
Perform
wizard
Fail
startup
after the
handling.)
If there is no water supply,
clear the humidifier
commissioning item. After
wizard startup, lift the low
liquid level detector. After
at least 5 seconds, choose
Running > Device Details
> Humidifier to check
that Low liquid level
states is Triggered.
Choose Running > Device
Details > Humidifier >
Advanced to check that
Humidifier pump control
states is On, indicating
that the humidifier is
functional.

Advertisement

loading