Section 7: Energy Management
Fig 7.3 Pressure switch setting
PURGE OFF (switch activated)
OFF
ON
105
100
95
90
85
85
80
Using an Electronic Pressure Switch for Purge Control
The best choice if using a pressure switch is to select an
electronic programmable type pressure switch which is
effectively a pressure transmitter and process controller
built into one device. While significantly more costly than
a standard pressure switch, an electronic programmable
pressure switch can be setup to provide a much more
customized operation. Typically, the dead band can be reduced
or eliminated so that an immediate reaction to changes, in
system pressure indicating air flow, can be obtained.
It is extremely important to understand that the purge may
only be shut off during periods of low or no demand. This
feature, if used otherwise, can result in permanent damage
to the desiccant beds resulting in loss of drying capacity
and possibly mechanical failure. The cartridges must not be
allowed to become fully saturated at any time.
The following schematic offers an overview of the devices
mentioned as they might be connected for use in controlling
a dryer's purge function. Please note that specific details
differ between device manufacturers, so in all cases the
manufacturer's specifications should be adhered to.
34
(pressure switch deactivation point)
PURGE ON (switch deactivated)
PIN 2
PIN 1 (puts out +5 VDC signal)
SIGNAL OUT
SIGNAL BACK
* Normally Closed, open to turn purge off
ADJUST TO SUIT SYSTEM
PURGE OFF (switch activated)
DRYER
CONTROLLER
PIN 2
PIN 1 (puts out +5 VDC signal)
SIGNAL OUT
SIGNAL BACK
* Normally Closed, open to turn purge off
Figure 7.4 Using an Electronic Pressure Switch for Purge Control
DRYER
CONTROLLER
PIN 2
PIN 1 (puts out
+5 VDC signal)
SIGNAL OUT
SIGNAL BACK
* Normally Closed, open to turn purge off
This setup is for example only. This configuration can be
amended, depending on application.
Heatless Desiccant Dryers |
DRYER
CONTROLLER
MANUAL SWITCH
(Field Installed)
N.C.*
PURGE ON
MANUAL SWITCH
(Field Installed)
N.O.
N.C.*
DC POWER
ELECTRONIC
SUPPLY
PRESSURE SWITCH
RELAY
N.O.
N.C.*
DC POWER
PROCESS
SUPPLY
CONTROLLER