E-18
SICAM Q80 7KG8080
Supply for AC/DC-variant
9.2
3-pol terminal
socket
9.3
Main Switch
ON/OFF
1. Switch ON: For both ON and OFF, press the main switch.
2. Switch OFF: For shutting the machine off, there is a delay before the device is actually off, since all procedures
running must be ended properly.
Storage cells and batteries
9.4
The system comes with long-lasting lithium batteries (Type BR2032) requiring no special maintenance.
9.5
Fuses
When selecting the breaker, both the switching capability and the suitability for AC as well as DC
voltage must be taken into account!
Specifications for the breakers installed are provided
Power Quality Recorder SICAM Q80 7KG8080, Operating instruction
E50417-B1074-C419-A2, Release 12.01.2015
The supply voltage for the AC/DC variant is routed through a 3-pin terminal socket. Wiring of this
terminal has to be performed by expert personnel.
The permitted supply voltage range is 110 V to 250 V DC or 100 V to 230 V AC at either 50 Hz or
60 Hz. If the device is supplied from the source to be measured, then measurement stops
automatically during longer power outages and restarts independently upon resumption of power.
For the AC-power supply of SICAM Q80 7KG8080, note the following:
The grounding is relevant with respect to the safety for the device. Also the grounding
ensures the measurement precision and the necessary electromagnetic compatibility
(EMC).
The input lead must have low impedance and sufficient cross-section area.
here
70
.