Technical data SICAM Q80 7KG8080
15.1
Parameter
General (at 25°C)
Ambient conditions
Signal inputs
Digital in/out
Power supply
rating voltage
rating frequency
rating power consumption
Fuses
UPS
capacitor
EMC
Interference resistance/
transient emissions
Protection degree
Weight
Dimensions
Ambient temp. range
Storage temperature
Interfaces
Memory capacity
Timer (internal RTC) crystal-
controlled real time clock
external synchronization
1 For permanent connection with the building installation, either Type 1 or Type 2 (Class I or II,
EN 61643-11) overvoltage protection is to be provided, with a protected voltage level of 1.5 kV.
2 For DC-operation, the breaking capacity must be selected to meet the deployment conditions.
Power Quality Recorder SICAM Q80 7KG8080, Operating instruction
E50417-B1074-C419-A2, Release 12.01.2015
Value
The normal ambient conditions according to EN 61010-1 apply (see
conditions
). These ambient conditions are can be broadened in accordance
69
with the statements made in these technical specs
4 x current [I]
4 x voltage [U]
8 x voltage [U]
4 binary inputs
4 relays outputs
12 V to 60 VDC
(±10%)
100 V bis 230 VAC / 110 V to 250
VDC
(±10%)
50 / 60 Hz
< 20 VA
< 12 W
1 A T @AC 250 V
1 A T @DC 300 V
buffer time:
1 second
class A
IP 20
approx. 1.9 kg
166 mm x 105 mm x 117 mm
-10 °C to 55 °C
-40 °C to 90 °C
Ethernet,
Modem
2 GB standard
up to 16 GB possible
± 1s/day
GPS, DCF, IRIG-B, NTP or other
SICAM Q80 7KG8080
Test conditions/ Remarks
7KG8080-0AA00-0AA0
7KG8080-0BA00-0AA0
7KG8080-1AA00-0AA0
7KG8080-1BA00-0AA0
7KG8080-0AA00-0AA0
7KG8080-1AA00-0AA0
7KG8080-0BA00-0AA0
7KG8080-1BA00-0AA0
AC with overvoltage category II
7KG8080-0BA00-0AA0
7KG8080-1BA00-0AA0
SIBA, e.g. type 1799200 or
SCHURTER 0001.2504
breaking capacity > 1500 A
factory settings
according IEC/EN 61326-1
according EN60529
(W x H x D) without top-hat rail
acc. to IEC 60688, no condensation
acc. to IEC 60688, outside < -15°C or >
+55°C only for short time recommended
RJ45 (TCP/IP), Modbus TCP
DSUB9
CF-Card
battery backed
GPS-input
Sync-input
Operating