E-76
SICAM Q80 7KG8080
Synchronization and time base
15.2
Parameter
balanced (default)
Drift
Ageing
Parameter
Supported formats
Precision
Jitter (max.)
Voltage level
Input resistance
Input connector
Shield potential
*PPS (pulse per second): signal is necessary, **using BCD information only
** from hardware version 7KG8080-XXX-CC
For description see
here
Power Quality Recorder SICAM Q80 7KG8080, Operating instruction
E50417-B1074-C419-A2, Release 12.01.2015
value typical
time base per device without external synchronization
20 ppm
time base per device with external synchronization signal
GPS
NMEA / PPS*
TTL (PPS*)
RS232 (NMEA)
1 k
(pull up)
DSUB-9 connector "GPS"
not isolated
42
min. / max.
Remarks
at 25°C (accuracy of internal time base)
10 ppm
50 ppm
at 25°C, 10 years
10 ppm
DCF77
IRIG-B
B000, B001, B003**
±1 µs
±8 µs
24 V
(H>18 V, L< 12 V
U
= 50 V
max
I
= 2.1mA)**
max
20 k
(pull up)
2-pin socket +
screw terminal connector
14..16 AWG, 0.2 mm² to 1.5 mm²
system ground
NTP
B002
version 4 (downwards
compatible)
<5 ms after ca. 12 h
---
---
Ethernet
---