Checking After Commissioning - Huawei FusionCol8000-E240 Quick Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

1. Initial Startup Flowchart
Start
Tap Start on the home screen.
Tap Confirm, and the barcode and
verification code are displayed.
Open the Service Expert app.
Choose StartUp > Offline
Activation on the app.
Enter the barcode and verification
code, and tap Generate PWD.
Enter the generated password on
the screen.
Tap Confirm. The Wizard Startup
screen is displayed.
Go to step 2.
12
Device Power-Off
1. On the home screen, tap Shutdown.
2. Turn off the general switch.
3. (Optional) If the device needs to be powered off for maintenance or for a long time, turn
off the device switch in the PDF.
13

Checking After Commissioning

Item
The foreign matter on the water pan and bottom plate is cleaned up.
The air filter is correctly installed according to the airflow direction marked on the
frame.
Condensate water in the water pan is drained smoothly.
All maintenance doors are closed.
When the ambient temperature is lower than 3°C, check the water in the
drainpipe and water pump.
2. Wizard Startup Flowchart
Start
Confirm precautions
and check items.
Yes
Select commissioning
items.
Yes
Commission the
indoor fan.
Succeeded
Commission the
spray system.
Succeeded
Commission the
exhaust fan.
Succeeded
Commission the
cooling system.
Succeeded
End
24
No
No
Failed
Failed
Failed
Failed
Check Result
□ Passed
□ Failed
□ Passed
□ Failed
□ Passed
□ Failed
□ Passed
□ Failed
□ Passed
□ Failed

Advertisement