Huawei FusionCol8000-E240 Quick Manual page 4

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

Materials delivered
with the unit
Optional component Motorized damper, electric heater, and T/H sensor
Local
Water pipe
procur
ement
Cable
2.3
Requirements for Maintenance Space
FDC Scenario
(1) Walls
(2) Indoor air supply vent sides
Refer to the material list.
Water refill pipe of the water tank: G 3/4 inch inner thread connector
(DN25)
Condensate drainpipe of the evaporator: G 3/4 inch inner thread
connector (DN25)
Water tank drainpipe: G 1-1/2 inch inner thread connector (DN50)
Condensate water pan drainpipe: G 1 inch inner thread connector
(DN32)
Floor drain pipe: G50
Primary power cable: 3 x 95 mm
Backup power cable: 3 x 95 mm
Unit: mm
2
(L1/L2/L3) + 50 mm
2
(L1/L2/L3) + 50 mm
Building Scenario
(3) Electric control boxes (4) Corridor module
3
2
(PE)
2
(PE)