Voltage Input Characteristics - LG G3F-AD3A User Manual

Programmable logic controller
Table of Contents

Advertisement

Chapter 2. SPECIFICATIONS
Digital
Output
Value
DC 0 ~ 10V
Analog
DC 1 ~ 5V
Input
DC-10 ~ 10V
DC 4 ~ 20
REMARK
1. The analog output value of over 4047 or –48(2047 or –2048) is fixed as 4047 or –48(2047 or –2048).
2. Keep the input voltage and current not to exceed +15V and 25mA.

2.4.1 Voltage Input Characteristics

1) G3F-AD3A, G4F-AD3A
For voltage input, the corresponding input selection switch of each channel should be set to "off".
- Off : Voltage
The voltage input range is selected in program.
Input selection switch has to be located at off.
(1)Voltage input range : DC 0 ~10V
Digital output value for input voltage is shown as follows.
Digital output value
Practical analog input range
2047
4047
2000
4000
1000
3000
0
2000
1000
-1000
-2000
0
-2048
-48
-0.12V
0V
0.952V
1V
-10.24V
-10V
3.808 ㎃
4
[Fig 2.1]
I/O Conversion Characteristics
Input selection switch
On
1 2 3 4 5 6 7 8
CH0
1 2 3 4 5 6 7
- 0 .12
0
2.5
-48
0
1000
2 - 8
5V
3V
0V
12
20
(This switch is located
on the side of module)
Number of channel
Analog input voltage (V)
5
7.5
10
2000
3000
4000
10.12V
10V
5V
5.048V
10.24V
10V
20.192 ㎃
10.12
4047

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

G4f-ad3aG6f-ad2a

Table of Contents