Chapter 3 Installation and wiring
3.2 Wiring
3.2.1 Wiring precautions
① Separate AC and external input signal of A/D module wiring not to be affected by
surge or induced noise in the AC.
② External wiring has to be at least AWG32 (0.3mm
of operating ambiance and/or allowable current.
③ Separate wiring from device and/or substances generating intense heat, and oil not to
make short-circuit which leads to damage and/or mis -operation.
④ Be careful not to connect external power supply with wrong polarity.
⑤ Separate external wiring sufficiently from high voltage and power supply cable not to
cause induced noise or malfunction of module.
3.2.2 Wiring examples
1) G6F-AD2A
① Voltage input
*1
*1
② Current input
*1
*1
*1: Use a two-core twisted pair shielded cable
*2 : If noise is expected, ground the cable and FG terminal as shown in figure.