Siemens SIMOTICS GP Operating Instructions Manual page 80

Horizontal and vertical induction motors
Table of Contents

Advertisement

Available languages

Available languages

CAUTION:
frequency described in the motor nameplate. The motor will operate
successfully under running conditions at rated load with a variation in the
voltage or the frequency up to the following:
1. When the variation in the voltage value does not exceed 10% above
or below the specified in the motor nameplate, with all phases
balanced.
2.
When the variation in the frequency value does not exceed 5%
above or below the specified in the motor nameplate.
3. When the sum of the voltage and the frequency values does not
exceed 10% above or below the specified in the motor nameplate
(provided frequency value variation does not exceed the 5%).
However, performance within these voltage and frequency variations
will not necessarily be in accordance with the standards established for
operation at rated voltage and frequency.
WARNING:
personnel, taking the following warnings into consideration:
1. The electrical supply shall be disconnected and preventive action
against accidental connection must be taken.
2. The motor shall be properly connected to a grounding circuit. Refer
to the NOM-001-SEDE and NEC or any other local electrical code.
Mounting options for terminal box in the FS 500
Standard Mounting
Unrestricted
Electrical supply must meet the values of voltage and
Any electrical maneuver must be carried out by qualified
Mounting to 45°
80
A5E43486667A_AB