ABB REF 610 Technical Reference Manual

ABB REF 610 Technical Reference Manual

Feeder protection relay
Hide thumbs Also See for REF 610:
Table of Contents

Advertisement

Quick Links

REF 610
Feeder Protection Relay
Technical Reference Manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB REF 610

  • Page 1 REF 610 Feeder Protection Relay Technical Reference Manual...
  • Page 3: Table Of Contents

    4.1.4.9. Inverse definite minimum time characteristics ...34 4.1.4.10.Settings ..............46 4.1.4.11.Technical data on protection functions ....58 4.1.5. Trip-circuit supervision .............62 4.1.6. Trip lockout function ............63 4.1.7. Trip counters for circuit-breaker condition monitoring ..64 © Copyright 2004 ABB Oy, Distribution Automation, Vaasa, FINLAND...
  • Page 4 5.1.3. Selecting adaptive sequence length ......140 5.2. Arc protection ................141 5.2.1. Arc protection with one REF 610 relay ......141 5.2.2. Arc protection with several REF 610 relays ....142 5.2.3. Arc protection with several REF 610 relays and one...
  • Page 5 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual 6. Ordering information ............144 7. References ................146 8. Abbreviations ................147 9. Check lists ................149...
  • Page 6: Introduction

    Introduction 1.1. About this manual This manual provides thorough information on the protection relay REF 610 and its applications, focusing on giving a technical description of the relay. Refer to the Operator’s Manual for instructions on how to use the Human-Machine Interface (HMI) of the relay, also known as the Man-Machine Interface (MMI), and to the Installation Manual for installation of the relay.
  • Page 7 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual • Four accurate current inputs • User-selectable rated frequency 50/60 Hz • Three normally open power output contacts • Two change-over signal output contacts and three additional change-over signal output contacts on the optional I/O module •...
  • Page 8: Guarantee

    REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual • Battery charge supervision • Continuous self-supervision of electronics and software. • Detachable plug-in unit 1.4. Guarantee Please inquire about the terms of guarantee from your nearest ABB representative.
  • Page 9: Safety Information

    REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Safety information Dangerous voltages can occur on the connectors, even though the auxiliary voltage has been disconnected. National and local electrical safety regulations must always be followed. The device contains components which are sensitive to electrostatic discharge.
  • Page 10: Instructions

    The start signals can be used for blocking co-operating protection relays and signalling. Fig. 3.3.-1 and Fig. 3.3.-2 represent REF 610 with the default configuration: all trip signals are routed to trip the circuit breaker. In Fig. 3.3.-1, the residual current is measured via a core-balance current transformer and the output contacts are connected to enable the use of the auto-reclose function.
  • Page 11 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Fig. 3.3.-1 Connection diagram, example 1...
  • Page 12 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Fig. 3.3.-2 Connection diagram, example 2...
  • Page 13: Technical Description

    Functional description 4.1.1. Product functions 4.1.1.1. Protection functions The protection functions of REF 610 with their IEC symbols and IEEE device numbers are presented in the table below: Table 4.1.1.1-1 IEC symbols and IEEE device numbers IEEE Device Function description...
  • Page 14: Outputs

    4.1.1.3. Outputs REF 610 is provided with three power outputs (PO1, PO2 and PO3), two signal outputs (SO1 and SO2) and three optional signal outputs (SO3, SO4 and SO5). Switchgroups SGR1...8 are used for routing internal signals from the protection stages, the external trip signal and signals from the auto-reclose function to the desired signal or power output.
  • Page 15: Time Synchronization

    REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual INTERNAL FAULT FAULT CODE :30 Fig. 4.1.1.7.-1 Permanent IRF In case of a warning, the relay will continue to operate with full or reduced functionality and the green indicator LED (ready) will remain lit as during normal operation.
  • Page 16: Measurements

    REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Time synchronization is always triggered on the rising edge of the digital input signal. The time is adjusted in steps of five milliseconds per synchronization pulse. The typical accuracy achievable with time synchronization via a digital input is +2.5...-2.5 milliseconds for second-pulse and +5...-5 milliseconds for minute-pulse...
  • Page 17 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Fig. 4.1.3.-1 Signal diagram...
  • Page 18: Protection

    REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual The functions of the relay are selected with the switches of switchgroups SGF, SGB, SGR and SGL. The checksums of the switchgroups are found under SETTINGS in the HMI menu. The functions of the switches are explained in detail in the corresponding SG_ tables.
  • Page 19: Overcurrent Protection

    REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual 4.1.4.2. Overcurrent protection The non-directional overcurrent protection detects overcurrent caused by phase-to-phase and phase-to-earth short circuits. When one or several phase currents exceed the set start value of the low-set stage, I>, the stage will generate a start signal after a ~ 55 ms’...
  • Page 20: Earth-Fault Protection

    REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Stage I>>> can be set out of operation in SGF3. This state will be indicated by dashes on the LCD and by “999” when the set start value is read via serial communication.
  • Page 21: Thermal Protection For Cables

    REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual It is possible to block the tripping of an earth-fault stage by applying a digital input signal to the relay. Note! Stages I > and I >> can be set to be blocked by the auto-reclose function.
  • Page 22 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual When the thermal capacity exceeds the trip level, θ >, the stage will generate a trip signal. The operate time, i.e. the time from when the stage starts until it trips, is determined by the time constant, τ, and depends on the cable (cable cross section...
  • Page 23 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual 100000 10000 1000 t[min] 1.05 Fig. 4.1.4.4.-1 Trip curves when no prior load...
  • Page 24 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual 100000 10000 1000 t[min] 1.05 Fig. 4.1.4.4.-2 Trip curves at prior load 0.7 x I...
  • Page 25 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual 100000 10000 1000 t[min] 1.05 Fig. 4.1.4.4.-3 Trip curves at prior load 1 x I...
  • Page 26: Phase Discontinuity Protection

    Local light detection requires the optional arc light detection hardware. The arc protection can be realized as a stand-alone function in a single REF 610 or as a station-wide arc protection including several REF 610 protection relays. If...
  • Page 27 Consequently, the REF 610 relays in the station can, for instance, be set to trip the circuit breaker of either the incoming or the outgoing feeder depending on the fault location in the switchgear.
  • Page 28: Auto-Reclose Function

    At a permanent fault, auto-reclosing is followed by definite tripping. A permanent fault must be located and cleared before the fault location can be re-energized. The auto-reclose (AR) function of REF 610 can be used with any circuit breaker suitable for auto-reclosing. The AR function provides three programmable...
  • Page 29 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual reclosing can be inhibited via a digital input (CB Close Inhibit). Inhibition of reclosing is checked only when necessary and can therefore not be used to prevent initiation or progression of a shot.
  • Page 30 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual As default, the AR function is not in use (number of auto-reclose shots = 0). The AR function can be activated either via the HMI or with SPA parameter S25 by setting the number of auto-reclose shots to 1, 2 or 3.
  • Page 31 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual 100 ms CB position closed Shot Due Shot Initiation I>> Trip Ext AR Initiation I> Trip I> start delay Open CB Command I> Start *) Io>> Trip Io> Trip Io> start delay Io>...
  • Page 32 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Inhibition of the auto-reclose function The AR function can be inhibited (AR Inhibit) by any of the following signals: • external AR inhibit signal • trip signal from the arc protection stage, ARC •...
  • Page 33 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Reclosing is inhibited and the CB Reclosing Failed signal generated also if an AR initiation signal is active, i.e. the fault has not been cleared, when reclosing begins. The duration of the reclosing command is settable (CB closing time). However,...
  • Page 34: Inverse Definite Minimum Time Characteristics

    REF 610 provides eight IDMT characteristics, of which four comply with the IEC 60255-3 and three with the IEEE C37.112 standard. One is a special characteristic according to ABB praxis and is referred to as RI.
  • Page 35 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Table 4.1.4.9-2 Values of constants α and β α β Time/current curve group Normal inverse 0.02 0.14 Very inverse 13.5 Extremely inverse 80.0 Long-time inverse According to the standard, the normal current range is 2...20 times the set start value at normal inverse, very inverse or extremely inverse characteristic.
  • Page 36 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual 0.05 0.09 0.08 0.07 0.06 0.05 0.04 0.03 0.02 5 6 7 8 20 I/I> Fig. 4.1.4.9.-1 Normal inverse-time characteristic...
  • Page 37 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual 0.09 0.08 0.07 0.06 0.05 0.05 0.04 0.03 0.02 5 6 7 8 9 20 I/I> Fig. 4.1.4.9.-2 Very inverse-time characteristic...
  • Page 38 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual 0.09 0.08 0.07 0.06 0.05 0.04 0.03 0.05 0.02 5 6 7 8 9 20 I/I> Fig. 4.1.4.9.-3 Extremely inverse-time characteristic...
  • Page 39 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual 0.05 5 6 7 8 20 I/I> Fig. 4.1.4.9.-4 Long-time inverse-time characteristic...
  • Page 40 Technical Reference Manual IDMT characteristics according to the IEEE C37.112 REF 610 provides three time/current curve groups which comply with the IEEE C37.112 standard: extremely inverse, very inverse and moderately inverse. The relationship between time and current is expressed as follows: ...
  • Page 41 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual 0.09 0.08 0.07 0.06 0.05 0.04 0.03 0.02 5 6 7 8 9 20 I/I> Fig. 4.1.4.9.-5 Extremely inverse-time characteristic...
  • Page 42 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual 0.09 0.08 0.07 0.06 0.05 0.04 0.03 0.02 5 6 7 8 9 20 I/I> Fig. 4.1.4.9.-6 Very inverse-time characteristic...
  • Page 43 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual 0.09 0.08 0.07 0.06 0.05 0.04 0.03 0.02 5 6 7 8 9 20 I/I> Fig. 4.1.4.9.-7 Moderately inverse-time characteristic...
  • Page 44 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual RI-type characteristic The RI-type characteristic is a special characteristic which is principally used for obtaining time grading with mechanical relays. The relationship between time and current is expressed as follows:...
  • Page 45 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual 0.05 0.09 0.08 0.07 0.06 0.05 0.04 0.03 0.02 5 6 7 8 20 I/I> Fig. 4.1.4.9.-8 RI-type characteristic...
  • Page 46: 10.Settings

    REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual 4.1.4.10. Settings There are two alternative setting groups available, setting groups 1 and 2. Either of these setting groups can be used as the actual settings, one at a time. Both groups have their related registers.
  • Page 47 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Table 4.1.4.10-1 Setting values Setting Description Setting range Default setting θ Alarm level of stage θ> 50...100% θ 95% θ > > > CBFP Operate time of CBFP 0.10...60.0 s 0.10 s...
  • Page 48 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Switchgroups and parameter masks The settings can be altered and the functions of the relay selected in the SG_ selector switchgroups. The switchgroups are software based and thus not physical switches to be found in the hardware of the relay.
  • Page 49 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual SGF1...SGF5 Switchgroups SGF1...SGF5 are used for configuring the desired function as follows: Table 4.1.4.10-2 SGF1 Default Switch Function setting SGF1/1 Selection of the latching feature for PO1 SGF1/2 Selection of the latching feature for PO2...
  • Page 50 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Table 4.1.4.10-3 SGF2 Default Switch Function setting SGF2/1 Operation mode of the start indication of stage I> SGF2/2 Operation mode of the start indication of stage I>> SGF2/3 Operation mode of the start indication of stage I>>>...
  • Page 51 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Table 4.1.4.10-5 SGF4 Default Switch Function setting SGF4/6 Operation mode of light signal output • When the switch is in position 1, the light signal output will be blocked by the trip signal from stage ARC.
  • Page 52 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Table 4.1.4.10-7 SGB1...SGB5 Default Switch Function setting SGB1...5/4 Switching between setting groups 1 and 2 using the digital input • 0 = the setting group cannot be changed using the digital input •...
  • Page 53 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Note! The external fault warning is always routed to SO2. Optional I/O card PS_I/O card Weighting PO3 SO1 factor SGR1...8/1 I> SGR1...8/2 t> SGR1...8/3 I>> SGR1...8/4 t>> SGR1...8/5 I>>> SGR1...8/6 t>>>...
  • Page 54 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Table 4.1.4.10-8 SGR1...SGR3 Default setting Switch Function SGR1...SGR3 SGR4...SGR5 SGR6...SGR8 SGR1...8/1 Start signal from stage I> SGR1...8/2 Trip signal from stage I> SGR1...8/3 Start signal from stage I>> SGR1...8/4 Trip signal from stage I>>...
  • Page 55 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Table 4.1.4.10-9 SGL1...SGL8 Switch Function Default setting SGL1...8/9 Trip lockout signal SGL1...8/10 Definite trip alarm signal from AR SGL1...8/11 Shot due signal from AR SGL1...8/12 Lockout signal from AR SGL1...8/13 CB position open SGL1...8/14...
  • Page 56 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Table 4.1.4.10-11SG2 Switch Function Default setting SG2/1 Blocking of tripping of stage I> at shot 1 SG2/2 Blocking of tripping of stage I>> at shot 1 SG2/3 Blocking of tripping of stage I>>> at shot 1...
  • Page 57 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Non-volatile memory settings The table below presents data which can be configured to be stored in the battery backed-up non-volatile memory. All of the functions mentioned below can be selected separately with switches 1...5 either via the HMI or the SPA bus.
  • Page 58: 11.Technical Data On Protection Functions

    REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual 4.1.4.11. Technical data on protection functions Table 4.1.4.11-1 Stages I>, I>> and I>>> Feature Stage I> Stage I>> Stage I>>> Set start value, I>, I>> and I>>> • at definite-time characteristic 0.30...5.00 x I...
  • Page 59 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Table 4.1.4.11-2 Stages I > and I >> Stage I > Stage I >> Feature Set start value, I > and I >> • at definite-time characteristic 1.0...100% I 5.0...400% I •...
  • Page 60 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Table 4.1.4.11-3 Stage θ> Feature Value Set full load current, I 0.30...1.50 x I θ Set alarm level, θ > 50...100% Trip level, θ > 100% Time constant, τ 1...200 min Operate time accuracy •...
  • Page 61 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual ArcSensitREF610_a Fig. 4.1.4.11.-1 Relative sensitivity of lens sensors Table 4.1.4.11-6 Auto-reclose function Feature Value Number of shots 0...3 CB Closing time 0.1...10 s Start delay of stage I> 0...300 s Start delay of stage I >...
  • Page 62: Trip-Circuit Supervision

    REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual 4.1.5. Trip-circuit supervision The trip-circuit supervision (TCS) detects open circuits, both when the circuit breaker is open and closed, and trip-circuit supply failure. The trip-circuit supervision is based on the constant current injection principle: by applying an external voltage, a constant current is forced to flow through the external trip circuit.
  • Page 63: Trip Lockout Function

    REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual closed. The opening contact, on the contrary, is to be connected in series with the external shunt resistor, which will enable trip-circuit supervision when the circuit breaker is open; see Fig. 4.1.5.-1.
  • Page 64: Trip Counters For Circuit-Breaker Condition Monitoring

    The monitoring function consists of four counters, which count the number of trip signals generated to the circuit breaker by REF 610. Every time a stage generates a trip signal, the corresponding counter value will be increased by one. The number of trips is stored in the non-volatile EEPROM memory.
  • Page 65: Commissioning Tests

    4.1.11.1. Function REF 610 features an integrated disturbance recorder for recording monitored quantities. The recorder continuously captures the curve forms of the currents as well as the status of both internal and digital input signals and stores these in the memory.
  • Page 66: 3.Control And Indication Of Disturbance Recorder Status

    REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual channels, referred to as digital signals, are start and trip signals from the protection stages, the alarm signal from stage θ>, the signals from the auto-reclose function and the digital input signals linked to the relay.
  • Page 67: 4.Triggering

    4.1.12. Recorded data of the last events REF 610 records up to five events. This enables the user to analyze the last five fault conditions in the electrical power network. Each event includes the measured currents, start durations and time stamp, for instance. Additionally, information on the number of starts, trips and auto-reclose shots is provided.
  • Page 68 1 and the number of auto-reclose shots by entering the value 2 into parameter V166. REF 610 collects data during fault conditions. When all start or thermal alarm signals have been reset or a stage trips, the collected data and time stamp will be stored as “EVENT1”...
  • Page 69: Communication Ports

    >, counting up to 255 4.1.13. Communication ports REF 610 is provided with an optical communication port (infrared) on the front panel. Rear communication is optional and requires a communication module, which can be provided with either a plastic fibre-optic, combined fibre-optic (plastic and glass) or RS-485 connection.
  • Page 70: Iec 60870-5-103 Remote Communication Protocol

    IrDA Standard specifications or using a specific front communication cable (ABB art. no 1MRS050698). The cable is connected to the serial RS-232 port of the PC. The optical stage of the cable is powered by RS-232 control signals. The cable has a fixed baud rate of 9.6 kbps.
  • Page 71 REF 610 will use the SPA bus protocol as default when the optional communication module is in use. The protocol selection is memorized and will therefore always be activated when the rear connection is in use.
  • Page 72 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Table 4.1.14-1 Information mapping of configuration set 1 and 2 Event reason Disturbance recorder E31/ Triggered/Cleared HMI Password E33/ Opened/Closed I> Start/Reset 1E1/ I> Trip/Reset 1E3/ I>> Start/Reset 1E5/ I>> Trip/Reset 1E7/ I>>>...
  • Page 73 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Table 4.1.14-1 Information mapping of configuration set 1 and 2 Event reason Trip Lockout/Reset 1E37/ 1E38 External Trip/Reset 1E39/ 1E40 CBFP Activated/ 1E41/ Reset 1E42 PO1 Activated/Reset 2E1/ PO2 Activated/Reset...
  • Page 74: Modbus Remote Communication Protocol

    PLCs. For the protocol definition, refer to “Modicon Modbus Protocol Reference Guide PI-MBUS-300 Rev. E”. The implementation of the Modbus protocol in REF 610 supports both the RTU and the ASCII link mode. Both the link mode and the line setting parameters are...
  • Page 75: 2.Profile Of Modbus Ref 610

    1 stop bit if parity is used; 2 stop bits if parity is not used Note! The turnaround time (response time) of REF 610 depends on the amount of data requested in a query. Therefore, the turnaround time can vary between approximately 20 and 100 milliseconds.
  • Page 76 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual The implementation of the Modbus protocol in REF 610 supports the following functions: Table 4.1.15.2-1 Supported application functions Function code Function description Read coil status Reads the status of discrete outputs.
  • Page 77 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Table 4.1.15.2-2 Supported diagnostic subfunctions Code Name Description Return slave no The number of messages addressed to the slave for which a response count response (neither a normal response nor an exception response) has not been sent since its last restart, clear counters operation or power up is returned in the response.
  • Page 78 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Note! If an “Illegal data value” exception response is generated when attempting to preset multiple registers, the contents of the register to which an illegal value has been imposed and of the following registers will not be changed. Registers which have already been preset will not be restored.
  • Page 79 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Special case 2: If the master tries to read the next unread fault record without entering selection code 1 again, the contents of the last read record will be returned.
  • Page 80 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Selection code 2: reading the oldest stored record By resetting the read pointer using selection code 2, the master can read the oldest stored event record. After this, the master can continue reading the following records using selection code 1, irrespective of whether they have been read before.
  • Page 81 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual (read-only) area and digital indication values from either the DI or coil (read-only) area. It is also possible to read the status of the DIs as packed 16-bit registers from both the IR and the HR area.
  • Page 82 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Table 4.1.15.2-5 Mapping of Modbus data HR/IR DI/Coil bit Value Description Writeable Comment address (.bit) address range Trip signal from stage I>> 409.06 1 = activated Trip signal from stage I>>...
  • Page 83: Open Cb Command/ 3E13/ X

    REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Table 4.1.15.2-5 Mapping of Modbus data HR/IR DI/Coil bit Value Description Writeable Comment address (.bit) address range Shot 2 411.12 1 = initiated Shot 2 CD 411.13 Shot 3 411.14...
  • Page 84 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Table 4.1.15.2-5 Mapping of Modbus data HR/IR DI/Coil bit Value Description Writeable Comment address (.bit) address range HMI password 414.12 1 = opened 0 = closed HMI password CD 414.13 414.14...
  • Page 85 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Table 4.1.15.2-5 Mapping of Modbus data HR/IR DI/Coil bit Value Description Writeable Comment address (.bit) address range Number of AR shots (shot 1) 0...255 Counter initiated by the digital input...
  • Page 86: Current I L1

    REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Structure 2 This structure contains data recorded during a fault sequence. Refer to section Fault records for the reading method. Table 4.1.15.2-6 Fault record Address Signal name Range Comment 1...2...
  • Page 87 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Structure 3 This structure contains Modbus event records. Refer to section Event records for the reading method. Table 4.1.15.2-7 Event record Address Signal name Range Comment 1...3 1 = read oldest...
  • Page 88: Dnp 3.0 Remote Communication Protocol

    All DNP parameters are stored on the external DNP 3.0 module. After parameterization with the Relay Setting Tool, REF 610 must be switched to the rear communication mode for at least 10 seconds in order for the DNP parameters to be replicated and stored onto the DNP module.
  • Page 89 SPA parameter 503V24. The pointers to the scaling factors for analogue objects are all 0 as default. Consequently, the DNP and Modbus analogue values of REF 610 are identical as default. All DNP process points can be edited using the Relay Setting Tool. Editing features include: •...
  • Page 90 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Table 4.1.16.3-1 Binary data DNP point Event Value Description Comment address class enable range Shot 3 1 = initiated CB position 1 = closed Definite trip alarm signal 1 = activated...
  • Page 91 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Table 4.1.16.3-3 Counters DNP point Event Description Deadband Value range address class enable Number of starts of stage I> 0...999 Number of starts of stage I>> 0...999 Number of starts of stage 0...999...
  • Page 92: 4.Dnp 3.0 Device Profile Of Ref 610

    REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual 4.1.16.4. DNP 3.0 device profile of REF 610 DNP V3.00 DEVICE PROFILE DOCUMENT Vendor Name: ABB Oy, Distribution Automation Device Name: REF 610 Highest DNP Level Supported Device Function For Requests...
  • Page 93 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual FILL OUT THE FOLLOWING ITEMS FOR SLAVE DEVICES ONLY Reports Digital Input Change Events when Reports time-tagged Digital Input Change no specific variation requested Events when no specific variation requested...
  • Page 94 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Table 4.1.16.4-1 Supported function codes Code Function Description Supported Operate Set previously selected output Respond with status of control point Direct operate Set output directly Respond with status of control point...
  • Page 95 Message fragment confirmation Response Response to request message Unsolicited Message Spontaneous message without request Counters of REF 610 can not be cleared using the DNP 3.0 protocol. Table 4.1.16.4-2 Supported objects REQUEST RESPONSE OBJECT (slave must parse) (master must parse)
  • Page 96 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Table 4.1.16.4-2 Supported objects REQUEST RESPONSE OBJECT (slave must parse) (master must parse) Function Qualifier Function Qualifier Object Variation Description Codes Codes Codes Codes group (dec) (hex) (dec) (hex) 32-Bit Binary Counter without...
  • Page 97 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Table 4.1.16.4-2 Supported objects REQUEST RESPONSE OBJECT (slave must parse) (master must parse) Function Qualifier Function Qualifier Object Variation Description Codes Codes Codes Codes group (dec) (hex) (dec) (hex) 32-Bit Counter Change Event...
  • Page 98 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Table 4.1.16.4-2 Supported objects REQUEST RESPONSE OBJECT (slave must parse) (master must parse) Function Qualifier Function Qualifier Object Variation Description Codes Codes Codes Codes group (dec) (hex) (dec) (hex) 16-Bit Frozen Analogue Input...
  • Page 99: 5.Ref 610-Specific Dnp Features

    Time synchronization If time synchronization (minute-pulse or second-pulse) of the relay’s real-time clock is realized via a digital input, the following applies to the DNP interface of REF 610: • Depending on the pulse type, either the date-to-minute or the date-to-second information of the DNP time synchronization message will be used.
  • Page 100 DNP3.0 module and the main CPU module of REF 610. In this case, REF 610 will automatically activate and reset the IIN2.3 bit. As events have been lost in both cases, the DNP 3.0 master should perform an integrity scan after the IIN2.3 bit has been reset.
  • Page 101 Collision avoidance occurs before message transmission. When preparing to transmit and the link is busy, REF 610 will first wait until the link becomes idle. After this, a backoff time will start. When the backoff time elapses, REF 610 will check the link again.
  • Page 102: Spa Bus Communication Protocol Parameters

    REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual To show the analogue value in primary units, and if I = 300 A and the accuracy of the analogue value = 1 A: 1. Take any unused scaling factor and set it to 300.
  • Page 103 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Table 4.1.17-1 Settings Actual Group/ Group/ Variable settings (R), Channel 1 Channel 2 Setting range channel 0 (R, W, P) (R, W, P) Operate time of stage I>>> 1S10 2S10 0.04...30.0 s...
  • Page 104 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Table 4.1.17-1 Settings Actual Group/ Group/ Variable settings (R), Channel 1 Channel 2 Setting range channel 0 (R, W, P) (R, W, P) Checksum, SGL 3 1S93 2S93 0...2097151 Checksum, SGL 4...
  • Page 105 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Recorded data Parameter V1 shows the stage which has caused the trip, parameter V2 the trip indication code, parameters V3...V8 show the number of starts of the protection stages, parameters V9...V12 the number of trips of the protection stages, and parameters V13...V24 the number of initiated auto-reclose shots.
  • Page 106 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Table 4.1.17-3 Recorded data: Channel 0 Recorded data Parameter (R) Value Number of trips of stage I> 0...65535 Number of trips of stage I>> 0...65535 Number of trips of stage I>>>...
  • Page 107 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Table 4.1.17-4 Recorded data: Channels 1...5 Event (R) Recorded data Value Channel 1 Channel 2 Channel 3 Channel 4 Channel 5 Earth-fault current 0...800% I Phase discontinuity 0...100% Thermal level at 0...106%...
  • Page 108 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Disturbance recorder Table 4.1.17-5 Parameters for the disturbance recorder Parameter Description R, W Value (channel 0) Remote triggering Clear recorder memory Sampling rate R, W 800/960 Hz 400/480 Hz 50/60 Hz...
  • Page 109 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Table 4.1.17-6 Disturbance recorder internal triggering and storing Default value of Default value of Default value of Weighting triggering edge, Event triggering storing mask, factor mask, V236 V238 V237 Start of stage I>...
  • Page 110 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Table 4.1.17-8 Control parameters Description Parameter R, W, P Value Resetting of relay state data 0 = reset E50 and E51 1 = reset only E50 2 = reset only E51...
  • Page 111 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Table 4.1.17-8 Control parameters Description Parameter R, W, P Value Data transfer rate (SPA), kbps V201 R, W 9.6/4.8 Rear communication V202 1 = rear connector activated Rear communication protocol...
  • Page 112 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Table 4.1.17-9 Inputs Parameter (R), Description Value channel 0 CB position 0 = undefined 1 = closed 2 = open 3 = undefined DI1 status DI2 status DI3 status 1) 2)
  • Page 113 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Table 4.1.17-10Output signals Recorded Status of the protection State of stage (R), functions (R), Value stages channel 0 channel 0 CB reclosing failed Shot due AR Lockout Table 4.1.17-11 Outputs...
  • Page 114 Description R, W Value range Default Explanation (channel 503) Unit address 503V1 R, W 0...65532 Address of REF 610 in the DNP 3.0 network Master address 503V2 R, W 0...65532 Address of the master station (destination address for unsolicited responses)
  • Page 115 R, W 0...255 Number of layer retransmissions on data retransmission link layer count Application layer 503V6 R, W 0...65535 ms 5000 Used when REF 610 confirmation sends messages with timeout confirmation request Application layer 503V7 R, W 0...255 Number of retransmission...
  • Page 116 Refer to section reporting mode 1 = immediate Unsolicited reporting start 2 = empty UR up under section Protocol 3 = empty UR parameters of REF 610. and enable UR Scaling factor 1 503V101 R, W 0...4294967296 Scaling factor 2 503V102 R, W 0...4294967296...
  • Page 117: 1.Event Codes

    REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual 4.1.17.1. Event codes Special codes have been determined to represent certain events, such as start and tripping of protection stages and different states of output signals. The events are stored in the event buffer of the relay. The maximum capacity of the buffer is 100 events.
  • Page 118 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Events possible to mask out: Table 4.1.17.1-4 Event codes E31...E34 Weighting Channel Event Description Default value factor Disturbance recorder triggered Disturbance recorder memory cleared HMI password opened HMI password closed...
  • Page 119 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Table 4.1.17.1-7 Event codes E25...E42 Weighting Channel Event Description Default value factor Start signal from stage θ> activated Start signal from stage θ> reset Alarm signal from stage θ> activated Alarm signal from stage θ>...
  • Page 120 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Table 4.1.17.1-9 Event codes E17...E26 Weighting Channel Event Description Default value factor DI1 activated DI1 deactivated DI2 activated DI2 deactivated DI3 activated DI3 deactivated DI4 activated DI4 deactivated DI5 activated...
  • Page 121: Self-Supervision (Irf) System

    4.1.18. Self-supervision (IRF) system REF 610 is provided with an extensive self-supervision system which continuously supervises the software and the electronics of the relay. It handles run-time fault situations and informs the user about an existing fault via a LED on the HMI and a text message on the LCD.
  • Page 122 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Table 4.1.18-1 IRF codes Fault code Type of fault Optional I/O module configuration error Power supply module faulty Power supply module unknown Hardware configuration error Communication module unknown Faulty configuration set (for IEC 60870-5-103)
  • Page 123: Relay Parameterization

    The input terminals of the optional I/O module are located on connection socket X3.1 (see tables 4.2.1-4 and 4.2.1-5). Note! REF 610 is provided with connection socket X3.1 only if the optional I/O module has been installed. Terminals X4.1/21-24 and X3.1/1-6 (optional) are digital input terminals (see table 4.2.1-5).
  • Page 124 (X4.1/3-4). Fig. 4.2.1.-1...Fig. 4.2.1.-3 present a rear view of REF 610, showing four connecting sockets: one for measuring transformers, one for the optional I/O module, one for power supply and one for optional serial communication.
  • Page 125 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual X2.1 X3.1 X4.1 X5.5 Fig. 4.2.1.-2 Rear view of REF 610 with the RS-485 communication module...
  • Page 126 Feeder Protection Relay 1MRS 755310 Technical Reference Manual X2.1 X3.1 X4.1 X5.8 Fig. 4.2.1.-3 Rear view of REF 610 with the DNP 3.0 communication module for RS-485 Table 4.2.1-1 Inputs for phase and earth-fault currents Function Terminal X2.1-1 X2.1-2 X2.1-3 X2.1-4...
  • Page 127 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Table 4.2.1-2 Auxiliary supply voltage Terminal Function X4.1-1 Input, + X4.1-2 Input, - Table 4.2.1-3 IRF contact Terminal Function X4.1-3 IRF, common X4.1-4 Closed; IRF, or U disconnected X4.1-5 Closed; no IRF, and U connected Table 4.2.1-4...
  • Page 128: Light Sensor Input Connections

    X5.2 (see table 4.2.2-1 and Fig. 4.2.1.-1). For further information on the arc protection, refer to section Arc protection. Note! REF 610 is provided with connection sockets X5.1 and X5.2 only if the optional communication module with light sensor inputs has been installed (refer to section Ordering information).
  • Page 129 Daisy-chain bus wiring scheme with 2-wire, half-duplex, multi-point communication. The maximum number of devices (nodes) connected to the bus where REF 610 is being used is 32, and the maximum length of the bus is 1200 meters.
  • Page 130 Shield GND Combined fibre-optic connection (plastic and glass) If REF 610 is provided with the optional fibre-optic communication module for plastic and glass fibre, the plastic fibre-optic cables are connected to terminals X5.3-RX (Receiver) and X5.3-TX (Transmitter) and the glass fibre-optic cables to terminals X5.4-RX (Receiver) and X5.4-TX (Transmitter).
  • Page 131 Daisy-chain bus wiring scheme with 2- or 4-wire, half-duplex, multi-point communication. The maximum number of devices (nodes) connected to the bus where REF 610 is being used is 32, and the maximum length of the bus is 1200 meters in optimum conditions and with slow communication speed.
  • Page 132 1MRS 755310 Technical Reference Manual When connecting REF 610 to the bus, a quality twisted pair shielded cable is to be used. The conductors of the pair are connected to A and B. If signal ground is being used for balancing potential differences between devices/nodes, a quality dual twisted pair shielded cable is to be used.
  • Page 133: Technical Data

    REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Table 4.2.3-7 Jumper numbering Terminal Function Signal Pull-up Data A (+ TX) Termination Pull-down Data B (- TX) Pull-up Data A (+ RX) Termination Pull-down Data B (- RX) 4-wire/2-wire...
  • Page 134 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Table 4.2.4-2 Power supply variation (temporary) • REF610AxxHxxx 85...110% of U (ac) 80...120% of U (dc) • REF610AxxLxxx 80...120% of U (dc) <9 W/13 W Burden of auxiliary voltage supply under quiescent...
  • Page 135 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Table 4.2.4-7 Signal output SO2, optional SO3, and IRF output Rated voltage 250 V ac/dc Continuous carry Make and carry for 3.0 s 10 A Make and carry for 0.5 s...
  • Page 136 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Table 4.2.4-12 Electromagnetic compatibility tests EMC immunity test level meets the requirements listed below 1 MHz burst disturbance test, class III According to IEC 60255-22-1 • Common mode 2.5 kV •...
  • Page 137 • 9.6 or 4.8 kbps (9.6 kbps with front communication cable) Auxiliary voltage REF 610 requires a secured auxiliary voltage supply to operate. The internal power supply of the relay forms the voltages required by the relay electronics. The power supply is a galvanically isolated (flyback-type) DC/DC converter.
  • Page 138: Application Examples

    REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Application examples 5.1. Auto-reclose function 5.1.1. Fast tripping and initiation of shot 1 using two protection stages In several applications, such as fuse-saving applications involving down-stream fuses, tripping and initiation of shot 1 should be fast (instantaneous or short-time delayed) and of shot 2 and 3, and definite tripping time delayed.
  • Page 139: Fast Tripping And Initiation Of Shot 1 Using Start Signals

    An alternative way to achieve fast tripping and shot initiation (typical for certain countries, such as Finland), is to use start signals from protection stages for shot initiation. The AR function of REF 610 can be initiated by the start signals from stages I> and I >.
  • Page 140: Selecting Adaptive Sequence Length

    REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Note! When using AR I> Start Delay and AR Io> Start Delay for shot initiation and the signal Open CB Command has been routed to the trip output contact, stages I> and I >...
  • Page 141: Arc Protection

    An arc protection with one REF 610 only (see Fig. 5.2.1.-1) is realized by installing two arc lens sensors, connected to the relay protecting the incoming feeder, to detect an arc on the busbar.
  • Page 142: Arc Protection With Several Ref 610 Relays

    (via the other lens sensor), however, it will generate a signal to the REF 610 protecting the incoming feeder. On detection of the signal, the REF 610 protecting the incoming feeder will trip the circuit breaker of the incoming...
  • Page 143: Rea 101

    Arc protection with several REF 610 relays and one REA 101 When realizing an arc protection with both REF 610 relays and an REA 101 (see Fig. 5.2.3.-1), the cable terminations of outgoing feeders are protected by REF 610 relays using one lens sensor for each relay.
  • Page 144: Ordering Information

    Feeder Protection Relay 1MRS 755310 Technical Reference Manual Ordering information When ordering REF 610 protection relays and/or accessories, please specify the following: • Order number • Quantity The order number identifies the protection relay type and hardware as described in the figures below and is labelled on the marking strip under the lower handle of the relay.
  • Page 145 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual The following accessories are available: Item Order number Semi-flush mounting kit 1MRS050696 1MRS050831 Inclined (/ 25 ) semi-flush mounting kit Wall mounting kit 1MRS050697 19” Rack mounting kit, side-by-side 1MRS050695 19"...
  • Page 146: References

    REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual References Other available manuals: • Operator’s Manual, 1MRS 755311 • Installation Manual, 1MRS 752265-MUM...
  • Page 147: Abbreviations

    REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Abbreviations ANSI American National Standards Institute Auto-reclose ASCII American Standard Code for Information Interchange Circuit breaker CBFP Circuit-breaker failure protection Change detect Central Processing Unit Cyclical Redundancy Check Current transformer...
  • Page 148 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Switchgroups for digital inputs Switchgroups for functions Switchgroups for programmable LEDs Switchgroups for output contacts SO1...SO5 Signal outputs Second-pulse Trip-circuit supervision User-defined register Unsolicited reporting...
  • Page 149: Check Lists

    REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Check lists Table 9.-1 Setting group 1 Group/ Default Customer’s Variable Channel 1 Setting range setting setting (R, W, P) Start value of stage I> 0.30...5.0 x I 0.30 x I Operate time of stage I>...
  • Page 150 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Table 9.-1 Setting group 1 Group/ Default Customer’s Variable Channel 1 Setting range setting setting (R, W, P) Checksum, SGB 5 1S75 0...1048575 Checksum, SGR 1 1S81 0...8388607 2108074 Checksum, SGR 2 1S82 0...8388607...
  • Page 151 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Table 9.-2 Setting group 2 Group/ Default Customer’s Variable Channel 2 Setting range setting setting (R, W, P) Time constant of stage θ> 2S22 1...200 min 1 min Alarm level of stage θ>...
  • Page 152 REF 610 Feeder Protection Relay 1MRS 755310 Technical Reference Manual Table 9.-3 Control parameters Parameter Default Customer’s Description Setting range (channel 0) setting setting Time setting for disabling V108 0...999 min 60 min new trip indications on the Operation indications on...
  • Page 153 REF 610 1MRS 755310 Feeder Protection Relay Technical Reference Manual Table 9.-4 Parameters for the disturbance recorder Parameter Default Customer’s Description Setting range (channel 0) setting setting External trigger signal's V241 0...31 checksum External trigger signal's V242 0...31 edge Checksum of external V243 0...31...
  • Page 156 ABB Oy Distribution Automation P.O. Box 699 FI-65101 Vaasa FINLAND Tel. +358 10 22 11 Fax. +358 10 224 1094 www.abb.com/substationautomation...

Table of Contents