Sharp JW-20CM User Manual page 229

Programmable controller
Table of Contents

Advertisement

(3) F-205
F-205
RCV
Symbol
Function
Operation
Range of n
Range of D
[*1]
Condition
Contents
of D
Communication
No response
from module [*2]
After
Communication
operation
jam [*3]
Communication busy
(waiting for response
from target station)
Nomal end
Abnomal end [*4]
(communication
error)
• Even addresses must always be used for indirect addressing (@∫0001, @b0173, etc. are
prohibited).
• For details of indirect addressing, see PC's programming manual.
• F-205 instruction must always be used in conjunction with the F-202 (OPCH) instruction.
• After turning ON the input signal of F-205, keep it ON until the finish of the execution of the
instruction. If the input signal is turned OFF during execution of the instruction, the instruction
13
ends in an incomplete condition. Under this condition, next, when an F-205 instruction is given, it
will come to a "communication jam," and the instruction will not be executed. Turn the power OFF
and then ON again for recovery.
[*1]
Setting range of "S" is for JW model PCs. For ZW model PCs, setting range is コ0000 to
19777.
[*2]
In case that the network module of the assigned module number is not installed.
[*3]
In case that the channel is used with the other SEND/RECEIVE instruction.
This instruction is executed after end of execution of the previously given instruction, and
flag sign is changed into "communication busy" from "communication jam."
[*4]
In case that response from target station does not come within the time-out time.
Receive Data
F-205
n
D
RCV
Specify the first address and byte count
of the receive data for transmission
across satellite net.
Specified station → D to D + n - 1 
000 to 377
(256 bytes for 000
(8)
]0000 to ]1577
@]0000 to @]1574
b0000 to b1777
@b0000 to @b1774
09000 to 09777
@09000 to @09774
:
:
99000 to 99777
@99000 to @99774
0000 to
1777
@E0000 to @E1774
E
E
When input signal is ON.
Unchanged
Zero
Carry
Error
contents
07357
07356
07355
0
0
0
0
1
0
0
1
0
1
[Explanation]
14003
F-202
OPCH
F-205
RCV
)
(8)
When the input condition of 14003 changes from OFF to ON,
this instruction reads 6 bytes of data from file 0's file area
beginning with file address 04000 on satellite net station 04,
via CH0 of port No. 2. The data read is stred to registers
19000 to 19005.
Specify target
station
Non-carry
Received data
07354
09000
01
1
0
09001
04
0
1
09002
07
09003
10
0
1
09004
20
09005
30
0
0
1
0
13
28
·
Instruction
S T R
F-202
2.0.04
0
04000
F-205
006
006
19000
Port 2
04
Sending
09000
09001
09002
Response
09003
09004
09005
Flag
P.2
C.0
S.04
0
04000
19000
File 0
01
04
07
10
20
30

Advertisement

Table of Contents
loading

This manual is also suitable for:

Jw-20rs

Table of Contents