2.4 Generator Connectivity

The UPS solution offers the possibility of connecting up an external diesel generator
through a specially designed supporting product, the Generator Connect Feeder Pillar.
This adaptation of the normal large feeder pillar allows a portable generator to be used as
a substitute for the mains supply in cases of extended power outages.
See section 12.6 for more information on the Generator Connect Feeder Pillar.

2.5 Electrical Information

Parameter
Input:
Voltage
Frequency
Current (at max battery
charging current)
Mains Input Circuit Breaker
Rating
Output:
Voltage
Frequency
1
Maximum Power
Waveform
Switching Time
Voltage Distortion
Efficiency
Battery Charging:
Charge Current
Temperature Compensation
Battery Type
Environment:
Operating Temperature
Operating Altitude
Operating Humidity
1
Power output de-rates in high ambient temperatures. See sections 4.1 and 12.5 for details.
Version
7
Last Editor
Ore Oluwatudimu
Document
UPS Solution General Handbook
Name
Copyright ã Siemens plc 2017 All Rights Reserved
230Vac (150Vac – 328Vac without switching to battery support)
50Hz / 60Hz Auto-detect (±5%)
FXM1100: 8A at 230Vac
FXM2000: 15A at 230Vac
20A at 230Vac
230Vac
50Hz / 60Hz Auto-detect (±5%)
FXM1100: 1100 W/VA
FXM2000: 2000 W/VA
Pure Sine Wave
<5ms
<3% THD
Normal mode (LINE): >98%
Battery support mode (INVERTER): >82%
10A
-5mV/°C/Cell
12V 55Ah Valve Regulated Lead Crystal
-25°C to +74°C
12000ft
Up to 95%
Table 2-2: UPS Solution Electrical Information
Page 11 of 76
TS008468
Infrastructure and Mobility, Traffic Solutions
Sopers Lane, Poole, Dorset
Value
ISSUED
Status
Date
31/01/2017
Doc. No.
667/HB/47750/000
BH17 7ER