12.3 Communicating with the UPS Solution

12.3.1 Three-Button Interface

The Alpha FXM UPS unit includes a simple three-button button interface and LCD display
for basic system interrogation while present on site.
Using the three buttons, CANCEL, SCROLL and SELECT, it is possible to access the
following menus:
Control Menu -
System Status Menu -
Alarm and Fault -
Event Status Menu -
For details on all the options available within these menus, please refer to the Alpha FXM
UPS Operating Manual – 667/HB/47760/000.
Access to many more system settings can only be achieved through the RS232 or LAN
interfaces as described in sections 12.3.2 and 12.3.3.

12.3.2 RS232 Interface

The Alpha FXM UPS unit's RS232 interface can be accessed via the female 9-way D-
type connector on the unit itself. Table 12-4 below lists the necessary connection details.
Connection Parameters
Duplex Mode
Handshaking
Baud Rate
Data Format
Default Password
The RS232 Interface's main menu screen gives the user access to four main subsections
as well as displaying status and fault / alarm information in the following format.
Version
7
Last Editor
Ore Oluwatudimu
Document
UPS Solution General Handbook
Name
Copyright ã Siemens plc 2017 All Rights Reserved
Control, program and adjust a limited number of system
options including forcing the UPS unit into 'INVERTER'
mode.
Measure various inputs, outputs and related system values
including the current battery voltage and estimated support
time available.
Disabled unless the UPS unit has a fault, these menus
display and fault or alarm flags that are currently active.
Allows the user to scroll through the last 25 items listed in the
UPS unit's 100-event log.
Half Duplex
Software Handshaking
2400 bps
8-bit Data, No Parity, 1 Stop Bit, No Flow Control
1111
Table 12-4: RS232 Interface Connection Information
Page 48 of 76
TS008468
Infrastructure and Mobility, Traffic Solutions
Required Setting
Status
ISSUED
Date
31/01/2017
Doc. No.
667/HB/47750/000