13.4.3 Replacing an Alpha UATS unit

The UPS Cabinet needs to be Isolated before carrying out any work on the UATS or UPS
connection shelves. Please Isolate the cabinet by following the instructions in Section
13.3
Once the Cabinet is Isolated and the UPS is completely switched off, the following steps
can be followed:
1. Test the input and output terminals to ensure that the unit is completely isolated
from Mains and UPS
2. Remove the Covers from both sides of the UATS Shelf
3. Remove the four cable looms from the UATS, ensuring that you know where they
came from.
4. Replace the UATS Shelf
5. Wire the Cable looms into the replacement UATS and replace all of the covers.
6. Switch the UPS back on and check that it's working properly.

13.5 Second Line Maintenance

It is recommended that undamaged parts are reused where possible.
All other parts must be sent for repair or disposal. Further details are held in the 'Global
Service Support Plan (ref. 667/PA/47750/000).
NOTE: Observe Anti-static Precautions at all times.
Faulty parts being returned must always be sent back in the original packaging if
available or in an approved anti-static packaging, along with a fully completed fault label,
to;
Logistics Spares Returns Centre
Siemens Mobility,
Traffic Solutions,
Coalfield Way,
Ashby Park,
Ashby de la Zouch,
LE65 1JD
Any queries should be directed to the Service Logistics Manager on (01530) 258181.
Version
7
Last Editor
Ore Oluwatudimu
Document
UPS Solution General Handbook
Name
Copyright ã Siemens plc 2017 All Rights Reserved
Infrastructure and Mobility, Traffic Solutions
Page 63 of 76
Status
TS008468
Date
Doc. No.
Sopers Lane, Poole, Dorset
BH17 7ER
ISSUED
31/01/2017
667/HB/47750/000

Advertisement

Table of Contents
loading

Table of Contents