Installation Precautions

Location and Ambient Requirements

The Toshiba ASD is intended for permanent installations only.
Installation should conform to the 2005 National Electrical Code — Article 110 (NEC)
(Requirements For Electrical Installations), all regulations of the Occupational Safety and
Health Administration, and any other applicable national, regional, or industry codes and
standards.
Select a mounting location that is easily accessible, has adequate personnel working space, and
adequate illumination for adjustment, inspection, and maintenance of the equipment (refer to 2005
NEC Article 110-13).
A noncombustible insulating floor or mat should be provided in the area immediately surrounding
the electrical system.
DO NOT mount the ASD in a location that would allow it to be exposed to flammable chemicals or
gases, water, solvents, or other fluids.
Avoid installation in areas where vibration, heat, humidity, dust, fibers, steel particles, explosive/
corrosive mists or gases, or sources of electrical noise are present.
The installation location shall not be exposed to direct sunlight.
Allow proper clearance spaces for installation. Do not obstruct the ventilation openings. Refer to
Figures 1
Except where otherwise specified, the ambient operating temperature range of the ASD is 14° to
122° F (-10° to 50° C).
See
Tables 4

Mounting Requirements

Only Qualified Personnel should install this equipment.
Install the unit in a secure and upright position in a well-ventilated area.
A noncombustible insulating floor or mat should be provided in the area immediately surrounding
the electrical system at the place where maintenance operations are to be performed.
As a minimum, the installation of the equipment should conform to the NEC Article 110
Requirements For Electrical Installations, OSHA, as well as any other applicable national, regional,
or industry codes and standards.
Installation practices should conform to the latest revision of NFPA 70E Electrical Safety
Requirements for Employee Workplaces.
It is the responsibility of the person installing the ASD or the electrical maintenance personnel to
ensure that the unit is installed into an enclosure that will protect personnel against electric shock.
4
through
4
on
pg. 21
for further information on ventilation requirements.
and
5
on
pg. 19
for additional information on installing the drive.