Installation Precautions
Location and Ambient Requirements
•
The ACE-tronics G9 ASD is intended for permanent installations only.
•
Installation should conform to the 2008 National Electrical Code — Article 110 (NEC)
(Requirements For Electrical Installations), all regulations of the Occupational Safety and Health
Administration, and any other applicable national, regional, or industry codes and standards.
•
Select a mounting location that is easily accessible, has adequate personnel working space, and
adequate illumination for adjustment, inspection, and maintenance of the equipment (refer to 2008
NEC Article 110-13).
•
DO NOT mount the ASD in a location that would produce catastrophic results if it were to fall from
its mounting location (equipment damage or injury).
•
DO NOT mount the ASD in a location that would allow it to be exposed to flammable chemicals or
gases, water, solvents, or other fluids.
•
Avoid installation in areas where vibration, heat, humidity, dust, fibers, metal particles, explosive/
corrosive mists or gases, or sources of electrical noise are present.
•
The installation location shall not be exposed to direct sunlight.
•
Allow proper clearance spaces for installation. Do not obstruct the ventilation openings. Refer to the
section titled
requirements.
•
The ambient operating temperature range of the ACE-tronics G9 ASD is 14° to 104° F
(-10° to 40° C).
Mounting Requirements
•
Only
Qualified Personnel
•
Install the unit in a secure and upright position in a well-ventilated area.
•
As a minimum, the installation of the equipment should conform to the 2008 National Electrical
Code — Article 110 (NEC), OSHA, as well as any other applicable national, regional, or industry
codes and standards.
•
Installation practices shall conform to the latest revision of NFPA 70E Electrical Safety Requirements
for Employee Workplaces.
•
It is the responsibility of the ASD installer/maintenance personnel to ensure that the unit is installed
into an enclosure that will protect personnel against electric shock.
4
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Installation and Connections on pg. 14
should install this equipment.
for additional information on ventilation
ACE-tronics G9 ASD Installation and Operation Manual