F609
Low-Current Detection Hysteresis Width
Program  Protection  Low Current
During a momentary low-current condition, this parameter provides a current
threshold level to which the low-current condition must return within the time
setting of
F612
or a Low-Current Trip will be incurred.
Low-Current Trip
Program  Protection  Low Current
This parameter Enables/Disables the low-current trip feature.
When enabled, the ASD will trip on a low-current fault if the output current of
the ASD falls below the level defined at
at F612.
Settings:
Disabled
Enabled
Low-Current Detection Current
Program  Protection  Low Current
With the Low-Current Trip (F610) parameter enabled, this function sets the
low-current trip threshold.
The threshold value is entered as a percentage of the maximum rating of the
ASD.
Low-Current Detection Time
Program  Protection  Low Current
With the Low-Current Trip (F610) parameter enabled, this function sets the
time that the low-current condition must exist to cause a trip.
Short Circuit Detection At Start
Program  Protection  Special Protection Parameters
This parameter determines when the system will perform an Output Short
Circuit test.
Note:
Selection 3 is recommended for high-speed motor applications.
Because of the low impedance of high-speed motors the
standard-pulse setting may result in a motor malfunction.
Settings:
Every Start (Standard Pulse)
Power On or Reset (Standard Pulse)
Every Start (Short Pulse)
Power On or Reset (Short Pulse)
178
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
F611
and remains there for the time set
ACE-tronics G9 ASD Installation and Operation Manual
Direct Access Number — F609
Parameter Type — Numerical
Factory Default — 10
Changeable During Run — Yes
Minimum — 1
Maximum — 20
Units — %
Direct Access Number — F610
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
Direct Access Number — F611
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — % (or A; see
F701
setting)
Direct Access Number — F612
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 255
Units — Seconds
Direct Access Number — F613
Parameter Type — Selection List
Factory Default — Every Start (standard
pulse)
Changeable During Run — No
F613