LCD Screen
Screen
Under-Current
ACE-tronics G9 ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
LED
Description
UC
With the Low-Current Trip
(F610) parameter enabled, the
output current of the ASD is
below the level defined at
F611
and remains there for a
time longer than the setting of
F612.
Possible Causes
• The ASD is improperly matched to the
application.
• Motor lead disconnected.
253