System Grounding
Proper grounding helps to prevent electrical shock and to reduce electrical noise. The ACE-tronics G9
ASD is designed to be grounded in accordance with Article 250 of the 2008 NEC or Section 10/Part
One of the Canadian Electrical Code (CEC).
The grounding conductor shall be sized in accordance with Article 250-122 of the NEC or Part One-
Table 6 of the CEC.
— T h e M e t a l O f C o n d u i t I s N o t A n A c c e p t a b l e G r o u n d —
The input, output, and control lines of the system shall be run in separate metal conduits and each shall
have its own ground conductor.
ASDs produce high-frequency noise — steps must be taken during installation to avoid the negative
effects of noise. Listed below are some examples of measures that will help to combat noise problems.
DO NOT install the input power wires and output power wires in the same duct or in parallel with
each other, and do not bind them together.
DO NOT install the input power wires, output power wires, and the wires of the control circuit in
the same duct or in parallel with each other, and do not bind them together.
Use shielded wires or twisted wires for the control circuits.
Ensure that the grounding terminals (G/E) of the ASD are securely connected to ground.
Connect a surge suppressor to every electromagnetic contactor and every relay installed near the
ASD.
Install noise filters as required.
Grounding Capacitor
The Grounding Capacitor plays a role in minimizing the effects of leakage current through the ASD
system and through ground paths to other systems. Leakage current may cause the improper operation
of earth-leakage current breakers, leakage-current relays, ground relays, fire alarms, and other sensors
— and it may cause superimposed noise on CRT screens.
The
Grounding Capacitor Switch
capacitance of the 3-phase input circuit. See figures 4, 5, 6, and
the leakage-reduction functionality and the methods used to change the capacitance value. The method
used is typeform-specific.
If using a 460-Volt 5 HP ASD or a 460-Volt ASD that is in the range of 7.5 HP to 25 HP, and the U/T1,
V/T2, and W/T3 connections to the motor are 100 meters or more in length, the ASD Carrier
Frequency must be set to 4 kHz or less when activating or deactivating the
Switch. ASD overheating may occur if the Carrier Frequency is set above 4 kHz when activating or
deactivating the
See
pg. 5
for more information on the
switch.
18
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
allows the user to quickly change the value of the leakage-reduction
Grounding Capacitor
Switch.
Grounding Capacitor Switch
7 on pg. 19
for an electrical depiction of
Grounding Capacitor
and
pg. 16
ACE-tronics G9 ASD Installation and Operation Manual
for the location of the