F464
Second Speed Loop Stabilization Coefficient
Program  Feedback  PG
During closed-loop operation, this parameter sets the response sensitivity of the
ASD when monitoring the output speed for control.
The larger the value entered here, the quicker the response to changes in the
received feedback.
Load Moment of Inertia 2
Program  Feedback  PG
This parameter is used for calculating accel/decel torque when compensating
for load inertia while operating in the Drooping Control mode.
Speed PID Switching Frequency
Program  Feedback  Feedback
While running, this parameter establishes the threshold speed setting that is
used to determine if PID control may engage or remain engaged if active.
V/I Input Bias
Program  Frequency  Speed Reference Setpoints
This parameter is used to fine-tune the bias of the V/I input terminals.
Note:
See note on
pg. 55
for additional information on the V/I terminal.
This setting may be used to ensure that the zero level of the input source (pot,
pressure transducer, flow meter, etc.) is also the zero level setting of the ASD
system.
This is accomplished by setting the input source to zero and adjusting this
setting to provide an output of zero from the ASD.
V/I Input Gain
Program  Frequency  Speed Reference Setpoints
This parameter is used to fine tune the gain of the V/I input terminals.
Note:
See note on
pg. 55
for additional information on the V/I terminal.
This setting may be used to ensure that the 100% level of the input source (pot,
pressure transducer, flow meter, etc.) is also the 100% level setting of the ASD
system.
This is accomplished by setting the input source to 100% and adjusting this
setting to provide an output of 100% from the ASD.
164
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Direct Access Number — F464
Parameter Type — Numerical
Factory Default — 1
Changeable During Run — Yes
Minimum — 1
Maximum — 9999
Direct Access Number — F465
Parameter Type — Numerical
Factory Default — 35
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Direct Access Number — F466
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F470
Parameter Type — Numerical
Factory Default — 127
Changeable During Run — Yes
Minimum — 0
Maximum — 255
Direct Access Number — F471
Parameter Type — Numerical
Factory Default — 129
Changeable During Run — Yes
Minimum — 0
Maximum — 255
ACE-tronics G9 ASD Installation and Operation Manual