F806
RS485 2-Wire ASD-to-ASD Communications
Program  Communications  Communication
The function of this parameter is 2-fold:
1) In a Master/Follower configuration and while communicating via
RS485 2-Wire, this parameter sets the ASD as the Master or the Follower.
2) This parameter determines the function of the ASD while operating as the
Master or the Follower. If operating as the Master ASD, an output parameter of
the Master ASD is used to control the Follower ASDs and is set here. If
operating as a Follower ASD, the ASD response if an error is incurred is set
here.
Note:
Select a Follower function here if
Master Output controller for any other ASD in the system.
Otherwise, an EOI failure will result.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Settings:
Follower (Decel Stop If Error Detected)
Follower (Continues Operation If Error Detected)
Follower (Emergency Off If Error Detected)
Master (Frequency Command)
Master (Output Frequency)
Master (Torque Reference)
Master (Torque Command)
Frequency Point Selection
Program  Communications  Communication Reference Adjust
This parameter is used to set the communications reference for scaling.
See
F811
F814
for additional information on this setting.
Note:
Scaling the communications signal is not required for all
applications.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Settings:
Disabled
RS485 (2-Wire — NOT USED)
RS485 4-Wire
Communication Card
ACE-tronics G9 ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
F826
is configured as a
Direct Access Number — F806
Parameter Type — Selection List
Factory Default — Follower (Decel Stop)
Changeable During Run — Yes
Direct Access Number — F810
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
F810
199