Toshiba ACE-tronics G9 ASD Installation And Operation Manual page 212

Adjustable speed drive
Hide thumbs Also See for ACE-tronics G9 ASD:
Table of Contents

Advertisement

F826
RS485 4-Wire ASD-to-ASD Communications
Program  Communications  Communication
The function of this parameter is 2-fold:
1) In a Master/Follower configuration and while communicating via
RS485 4-Wire, this parameter sets the ASD as the Master or the Follower.
2) This parameter determines the function of the ASD while operating as the
Master or the Follower. If operating as the Master ASD, an output parameter of
the Master ASD is used to control the Follower ASDs and is set here. If
operating as a Follower ASD, the ASD response if an error is incurred is set
here.
Note:
Select a Follower function here if
Master Output controller for any other ASD in the system.
Otherwise, an EOI failure will result.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Settings:
Follower (Decel Stop If Error Detected)
Follower (Continues Operation If Error Detected)
Follower (Emergency Off If Error Detected)
Master (Frequency Command)
Master (Output Frequency)
Master (Torque Reference)
Master (Output Torque)
RS485 4-Wire Protocol Selection (TSB/ModBus)
Program  Communications  Communication
This parameter sets the communications protocol for ASD-to-ASD
communications.
Settings:
Toshiba
Modbus
Communications Option (DeviceNet/Profibus) Setting 1
Program  Communications  Communication
While using the DeviceNet/Profibus communications protocol, this parameter
allows the user to select the read and write information communicated between
the ASD and the Host.
Read information may include the ASD fault status, ASD speed, ASD MAC
ID, etc. Write information may include Enable/Disable DeviceNet commands,
Forward run, ACC/DEC command, etc.
See the DeviceNet Option Instruction Manual (P/N 58683) for additional
information on this parameter.
Settings:
0 – 7
202
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
F806
is configured as a
ACE-tronics G9 ASD Installation and Operation Manual
Direct Access Number — F826
Parameter Type — Selection List
Factory Default — Follower (Decel Stop)
Changeable During Run — Yes
Direct Access Number — F829
Parameter Type — Selection List
Factory Default — Toshiba
Changeable During Run — Yes
Direct Access Number — F830
Parameter Type — Selection List
Factory Default — 0
Changeable During Run — Yes
F830

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents