Toshiba ACE-tronics G9 ASD Installation And Operation Manual page 249

Adjustable speed drive
Hide thumbs Also See for ACE-tronics G9 ASD:
Table of Contents

Advertisement

Sel. No.
NO NC
Stop Limit-Switch Forward — Activating this terminal applies the Stop command. The deceleration rate is set at
Stop Limit-Switch
138 139
parameter F284.
Slow-Speed Limit-
Slow-Speed Limit-Switch Reverse — Activating this terminal applies the modified Upper-Limit Slow Speed
140 141
Switch
setting of
Stop Limit-Switch Reverse — Activating this terminal applies the Stop command. The deceleration rate is set at
142 143
parameter F286.
144
Emergency Lift — Activating this terminal initiates the
144 145
the activation. This feature requires that the
Timed Run — Activating this terminal outputs the commanded speed (from RR, Communications, etc.) for the
146 147
duration of the
External Fault — In a multiple ASD configuration a faulted ASD signals the remaining ASDs that a fault has
148 149
occurred and shuts down the non-faulted ASDs. The non-faulted ASDs receive an External Fault signal via this
terminal from the faulted ASD.
Creep Speed
Creep Speed 1 Command — Activating this terminal modifies the output frequency of the ASD by multiplying
1 Command
150 151
the commanded frequency by the setting at the
for the number of pulse counts of the
Creep Speed 2 Command — Activating this terminal modifies the output frequency of the ASD by multiplying
152 153
the commanded frequency by the setting at the parameter. The modified output is allowed to run for the number of
pulse counts of the
Brake Failure — This terminal is activated via a transducer in the event that, during closed-loop operation, encoder
154 155
pulses are detected while the brake is applied.
Super Creep — Terminal activation rotates the motor for the amount of encoder pulses set at the
Count
156 157
Available in closed-loop operation only.
Note: NO/NC = Normally Open/Normally Closed. Selection numbers are used when selecting using communications.
ACE-tronics G9 ASD Installation and Operation Manual
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Table 7. (Continued) Discrete Input Terminal Assignment Selections and Descriptions.
F293
and the modified Deceleration setting of parameter
Timed-Run Run-Time
Super Creep Pulse Count
parameter at the frequency setting of
Terminal Selection Descriptions
Emergency-Lift
Emergency-Lift
function be enabled at F656.
setting.
Creep Multiplier 1
Super Creep Pulse Count
parameter. This setting is ignored if Creep Multiplier #1 is active.
Super Creep Speed
F285
for the duration of the activation.
function and continues for the duration of
parameter. The modified output is allowed to run
parameter.
parameter.
Super Creep Pulse