Toshiba ACE-tronics G9 ASD Installation And Operation Manual page 200

Adjustable speed drive
Hide thumbs Also See for ACE-tronics G9 ASD:
Table of Contents

Advertisement

F688
MON 1 Voltage/Current Output Switching
Program  Terminal  Analog Output Terminals
This parameter is used to set the output signal type of the MON1 output
terminal.
Settings
-10 V – +10 V
0 – 10 V
0 – 20 mA
MON 1 Output Gradient Characteristic
Program  Terminal  Analog Output Terminals
This parameter sets the output response polarity of the MON1 output terminal.
The MON1 output terminal response may be set to respond inversely (-) or
directly (+) to the input signal.
See parameter
F672
for additional information on this setting.
Settings:
Minus (Negative Gradient)
Plus (Positive Gradient)
MON 1 Bias Adjustment
Program  Terminal  Analog Output Terminals
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the MON1 terminal.
Set the assigned function of parameter
to a zero output.
See parameter
F672
for additional information on this setting.
MON 2 Voltage/Current Output Switching
Program  Terminal  Analog Output Terminals
This parameter is used to set the output signal type of the MON2 output
terminal.
See parameter
F674
for additional information on this setting.
Settings
-10 V – +10 V
0 – 10 V
0 – 20 mA
MON 2 Output Gradient Characteristic
Program  Terminal  Analog Output Terminals
This parameter sets the output response polarity of the MON2 output terminal.
The MON2 output terminal response may be set to respond inversely (-) or
directly (+) to the input signal.
See parameter
F672
for additional information on this setting.
Settings:
Minus (Negative Gradient)
Plus (Positive Gradient)
190
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
F672
to zero and then set this parameter
Direct Access Number — F688
Parameter Type — Selection List
Factory Default — 0 – 10V
Changeable During Run — Yes
Direct Access Number — F689
Parameter Type — Selection List
Factory Default — Plus
Changeable During Run — Yes
Direct Access Number — F690
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -10.0
Maximum — 100.0
Units — %
Direct Access Number — F691
Parameter Type — Selection List
Factory Default — 0 – 10V
Changeable During Run — Yes
Direct Access Number — F692
Parameter Type — Selection List
Factory Default — Plus
Changeable During Run — Yes
ACE-tronics G9 ASD Installation and Operation Manual
F692

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents