F511
Express Stop Decel Time
Program  Special  Accel/Decel 1 – 4
This parameter specifies the time in seconds for the output of the ASD to go
from the Maximum Frequency to 0.0 Hz during an Express Stop. When
enabled at F493, this setting is used as an alternate deceleration time.
The Accel/Decel Pattern may be set using F512.
This parameter may be further defined by the settings of
Note:
A deceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads. Automatic
Accel/Decel, Stall, and Ridethrough settings may lengthen the
actual deceleration times.
Express Stop Acceleration/Deceleration Pattern
Program  Special  Accel/Decel 1 – 4
This parameter enables a user-selected preprogrammed output profile that
controls the acceleration and deceleration pattern during an Express Stop.
See
F502
for additional information on this parameter.
Settings:
Linear
S-Pattern 1
S-Pattern 2
Acceleration/Deceleration Switching Frequency 2
Program  Special  Accel/Decel Special
This parameter sets the frequency at which the acceleration control is switched
from the Accel #2 profile to the Accel #3 profile during a multiple-acceleration
profile configuration.
Plugging Acceleration Time
Program  Special  Accel/Decel 1 – 4
This parameter specifies the time in seconds for the output of the ASD to go
from 0.0 Hz to the Maximum Frequency during Plugging. When enabled at
F494, this setting is used as an alternate acceleration time.
The Plugging Acc/Dec Pattern may be selected at F516.
This parameter may be further defined by the settings of
See
F494
for additional information on the Plugging function.
Note:
An acceleration time shorter than that which the load will allow
may cause nuisance tripping and mechanical stress to loads.
Automatic Accel/Decel, Stall, and Ridethrough settings may
lengthen the actual acceleration times.
174
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Direct Access Number — F511
Parameter Type — Numerical
Factory Default — 1.5
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000
Units — Seconds
F506
– F509.
Direct Access Number — F512
Parameter Type — Selection List
Factory Default — Linear
Changeable During Run — Yes
Direct Access Number — F513
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F514
Parameter Type — Numerical
Factory Default — 1.5
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000
Units — Seconds
F506
– F509.