1MRK 511 403-UEN Rev. L
IEC140000140 V1 EN-US
Figure 12:
Switch to the Protocol Specific tab. Here, all the IEEE C37.118 message types can be seen. If
the HeaderFrame is not included, ask the PMU to send the header frame via the Send Header
Frame command (Previous stage). Open each message type and observe the content of each
message.
Bay control REC670
Commissioning manual
Drop-down menu with commands for testing the PMU
© 2017 - 2022 Hitachi Energy. All rights reserved
Establishing connection and verifying the IEEE C37.118/1344 communication
Section 9
IEC140000140-1-en.vsd
67