Fujitsu BACnet UTY-VBGX Instruction Manual page 61

Gateway for vrf system
Table of Contents

Advertisement

BACnet
®
Gateway for VRF System
5.3.38 IU_rr_uu_FanSpeed_Status (Multistate Input Object Type)
Indoor unit air flow setting status can be monitored.
Property Identifier
Object_Identifier
Object_Name
Object_Type
Present_Value
Description
Device_Type
Status_Flags
Event_State
Reliability
Out_Of_Service
Number_Of_States
State_Text
Time_Delay
Notification_Class
Alarm_Values
Fault_Values
Event_Enable
Acked_Transitions
Notify_Type
Event_Time_Stamps
Profile_Name
* Only available when specific object has a Notification Class configured
Fan Speed status table
Fan speed status can be read using the values in the following correspondence table.
Pesent_Value Contents displayed in State_Text
1
Low
2
High
3
Med
4
Auto
Property Datatype
BACnetObjectIdentifier
CharacterString
BACnetObjectType
Unsigned
CharacterString
CharacterString
BACnetStatusFlags
BACnetEventState
BACnetReliability
BOOLEAN
Unsigned
BACnetArray[N] of
CharacterString
Unsigned
Unsigned
List of Unsigned
List of Unsigned
BACnetEventTransitionBits
BACnetEventTransitionBits
BACnetNotifyType
BACnetArray[N] of
BACnetTimeStamp
CharacterString
Copyright© 2010-2017 Fujitsu General Limited - All rights reserved
INSTRUCTION MANUAL r1.3.2 eng
Value
(Multistate Input, 11rruu)
"IU_rr_uu_FanSpeed_Status"
MULTISTATE_INPUT (13)
1 ~ 7
-
-
{FALSE, FALSE/TRUE, FALSE, FALSE}
STATE_NORMAL (0)
NO_FAULT_DETECTED (0),
UNRELIABLE_OTHER (7)
FALSE
7
Check Fan Speed status below
-
-
-
-
-
-
-
-
-
Pesent_Value
Contents displayed in State_Text
5
Quiet
6
Med-Low
7
Med-High
UTY-
ASHRAE
VBGX
R
R
R
R
R
R
R
R
O
-
O
-
R
R
R
R
O
R
R
R
R
R
O
R
O
R*
O
R*
O
R*
O
R*
O
R*
O
R*
O
R*
O
R*
O
-
61/103