Fujitsu BACnet UTY-VBGX Instruction Manual page 97

Gateway for vrf system
Table of Contents

Advertisement

BACnet
®
Gateway for VRF System
8.7.4 Signals Viewer
Check the current signal values on both: BACnet and VRF network side (connection to the VRF network and/or
BACnet client is required).
The Signals Viewer can be used even though only one system is connected to the gateway, BACnet or Fujitsu AC.
Therefore, it becomes convenient for supervision and testing the system.
In order to force a specific value to a signal, double-click the corresponding BACnet Server Value or Fujitsu VRF
Value cell in the table. Notice that grey cells can't be read or written. Changing its value in this way, will make:
The content of the corresponding object will be changed to this value.
If the signal is write-enabled, it will trigger a suitable command to Fujitsu AC system.
Copyright© 2010-2017 Fujitsu General Limited - All rights reserved
INSTRUCTION MANUAL r1.3.2 eng
97/103